West Control Solutions KS98-1 User Manual
Page 301
Digital outputs:
slotid
0 = correct module fitted
1 = wrong module fitted
fail_a
0 = no measurement error at channel a detected
1 = measurement error at channel a detected; e.g. sensor break
fail_b
0 = no measurement error at channel b detected
1 = measurement error at channel b detected; e.g. sensor break
Analog outputs:
Inp_a
measurement value channel a
Inp_b
measurement value channel b
Parameter
Beschreibung
Values
Default
x1a in
Measured value correction Inp_a, P1 input value
Real
0
x1aOut
Measured value correction Inp_a, P1 output value
0
x2a in
Measured value correction Inp_a, P2 input value
100
x2aOut
Measured value correction Inp_a, P2 output value
100
x1b in
Measured value correction Inp_b, P1 input value
0
x1bOut
Measured value correction Inp_b, P1 output value
0
x2b in
Measured value correction Inp_b, P2 input value
100
x2bOut
Measured value correction Inp_b, P2 output value
100
Configuration
Description
Values
Default
Typ_a
Typ_b
Type L -200...900 °C
00
30
Type J -200...900 °C
01
Type K -200...1350 °C
02
Type N -200...1300 °C
03
Type S -50...1760 °C
04
Type R -50...1760 °C
05
Type T -200...400 °C
06
Type W(C) 0...2300 °C
07
Type E -200...900 °C
08
Type B 0...1820 °C
09
Type D 0...2300 °C
10
Voltage 0...30mV
27
Voltage 0...100mV
28
Voltage 0...300mV
29
Standard signal 0...20mA
30
Standard signal 4...20mA
31
Fail_a
Fail_b
Switched off
0
1
Upscale, Inp_a (Inp_b) = x100_a (x100_b)
1
Downscale, Inp_a (Inp_b) = x0_a (x0_b)
2
Substitute value, Inp_a (Inp_b) = XaFail (XbFail)
3
Xakorr
Xbkorr
Measured value correction Inp_a (b) switched off
0
0
Measured value correction Inp_a (b) effective
1
Unit_a
Unit_b
Unit of the measured value of Inp_a (b) = °C
1
1
Unit of the measured value of Inp_a (b) = °F
2
STK_a
STK_b
Internal temperature compensation
1
1
External temperature compensation
2
x0_a(b)
Physical value Inp_a (Inp_b) at 0%
Real
0
x100_a(b)
Physical value Inp_a (Inp_b) at 100%
Real
100
Xa(b)Fail
Physical value Inp_a (Inp_b) at 0%
Real
0
Tfm_a(b)
Filter time constant of _a (Inp_b) in seconds
Real
0,5
Tkrefa(b)
Reference temperature for Inp_a(b) at STK_a(b)
Real
0
Modular I/O - extension-modules
9499-040-82711
III-301
TC_INP (analog input card TC, mV, mA)