Inputs/outputs, Configuration parameters, Parameters – West Control Solutions KS98-1 User Manual
Page 149
Alarm with offset (
x1 - x0):
x1 can be shifted by means of x0. This corresponds to the offset of alarm limits (L1, L2, H1 and H2) in par-
allel to the x-axis.
Inputs/outputs
Analog inputs
x1
Input value to be monitored
H1
High alarm 1
L1
Low alarm 1
Digital outputs
L1
Low alarm 1 - is logic 1 with
x1 < L1
L2
Low alarm 2 - is logic 1 with
x1 < L2
H1
High alarm 1 - is logic 1 with
x1 < H1
H2
High alarm 2 - is logic 1 with
x1 < H2
Analog output
y1
Calculated and limited input signal
x1.
Configuration parameters:
Parameter
Description
Range
Default
Select
Selection of variable to be
monitored
x1
x1
t
D alarm
dx1/dt
Alarm with offset
x1-x0
Parameters:
Parameter
Description
Range
Default
H2
High alarm 2
-29 999 ... 999 999
9999
L2
Low alarm 2
-29 999 ... 999 999
-9999
x0
Offset x0
-29 999 ... 999 999
0
Xsd
Switching hysteresis
0 ... 999 999
1
Limit value signalling and limiting
9499-040-82711
III-149
ALLV ( alarm and limiting with variable limits (No. 41))
Xsd
min
max
L1, L2
H1, H2
x
Fig. 13 Switching hysteresis and alarm limits:
+x
0
-x
0
x
y
Fig. 14 Offset of the alarm limits