Csend 184, Send module 184 – West Control Solutions KS98-1 User Manual
Page 184
Parameter and configuration data
Configuration
Description
Range
Default
NodeId
Node address of the sending KS98-1 (The sending KS98-1 is adjusted accordingly in engineering tool window
"CANparameter ".) r see *1
* 1) The node address of the sending KS98-1 is adjustable in engineering tool window "CANparameter” or via the
instrument parameters on the front panel (during off-line mode).
III-12.2
CSEND (Send mod. blockno.'s 21, 23, 25, 27 - (No. 57))
Function CSEND provides data for other KS98-1 units on the CANopen bus. The data can be read by the other
multifunction units using the CRCVfunction.
Inputs and outputs
Analog inputs
X1...X9
Analog values 1 to 9, which are sent.
Digital inputs
di1...di9 Digital values 1 to 16, which are sent.
Digital output
valid
0 = invalid data (e.g. no KS98-1 but only KS 98-1)
1 = data could be received
Parameter und Konfigurationsdaten
Configuration
Description
Range
Default
delta
Change from which a new send operation is started.
0,000...999 999
0,1
a
Transmission is at intervals of 200ms.
Note that there is a risk of data loss for values which are available only during 100 ms.
KS 98-1- KS 98-1 cross communication (CANopen)
9499-040-82711
III-184
CSEND (Send mod. blockno.'s 21, 23, 25, 27 - (No. 57))
Dev. data
Langu.
21 23 25 27
(
,
,
)