Inputs/outputs, Configuration – West Control Solutions KS98-1 User Manual
Page 113
Inputs/outputs
Digital input
d1
This signal is output with a delay at output
z1 and negated at output not z1.
Analog inputs
T1
Delay time T1 [s], by which the positive signal of
d1 is delayed, when Mode = Inputs.
T2
Delay time T2 [s]
, b
y which the negativ
e signal o
f
d2 is delayed, when Mode = Inputs.
Digital outputs
z1
Delayed input signal
d1.
not z1
Inverted delayed input signal
d1.
Configuration:
Configuration Description
Range
Default
Mode
Source of delay times
parameters T1 and T2
Parameters
r
Inputs T1 and T2
Inputs
The pulse duration accuracy is dependent of the time group to which the function is assigned.
It is an integer multiple of the sampling interval adjusted for this block (100, 200, 400, 800ms).
Example:
T1 = 0,7s with assignment to
- sample time 100ms means, delay time of the positive flank is 0,7s.
- sample time 200ms means, delay time of the positive flank is 0,8s.
- sample time 400ms means, delay time of the positive flank is 1,2s.
- sample time 800ms means, delay time of the positive flank is 1,6s.
Example with different delay time T1 and T2
Logic functions
9499-040-82711
III-113
TIME1 (timer (No. 69))
Input
Output
Output
Output
Output
Output
Output
d1
z1
z1
z1
z1
z1
z1
T1 = 1
T2 = 1
T1 = 1
T2 = 2
T1 = 1
T2 = 3
T1 = 1
T2 = 4
T1 = 2
T2 = 1
T1 = 3
T2 = 1
T1
T1
T1
T2
T2
T1
T2
T2
T1
T1
T2
T2
T1
T1
T2
T2
T1
T2
T1
T1
T2
T1
T2
T2
Fig. 111