West Control Solutions KS98-1 User Manual
Page 306

Parameter
Description
Value
Default
x1a in
Measured value correction Inp_a, P1 input value
Real
0
x1aOut
Measured value correction Inp_a, P1 output value
0
x2a in
Measured value correction Inp_a, P2 input value
100
x2aOut
Measured value correction Inp_a, P2 output value
100
x1b in
Measured value correction Inp_b, P1 input value
0
x1bOut
Measured value correction Inp_b, P1 output value
0
x2b in
Measured value correction Inp_b, P2 input value
100
x2bOut
Measured value correction Inp_b, P2 output value
100
Configuration
Description
Value
Default
Typ_a
Voltage 0...10V
0
0
Voltage -50...1500mV
1
Fail_a
Switched off
0
1
Upscale, Inp_a = x100_a
1
Downscale, Inp_a = x0_a
2
Substitute value, Inp_a = XaFail
3
Xakorr
Measured value correction Inp_a switched off
0
0
Measured value correction Inp_a effective
1
Typ_b
Voltage 0...10V
0
0
Voltage -50...1500mV
1
Fail_b
Switched off
0
1
Upscale, Inp_b = x100_b
1
Downscale, Inp_b= x0_b
2
Substitute value, Inp_b = XbFail
3
Xbkorr
Measured value correction Inp_b switched off
0
0
Measured value correction Inp_b effective
1
a0_a
Physical value Inp_a at 0%
Real
0
x100_a
Physical value Inp_a at 100%
Real
100
XaFail
Substitute value with sensor error at Inp_a
Real
0
Tfm_a
Filter time constant of Inp_a in seconds
Real
0,5
x0_b
Physical value Inp_b at 0%
Real
0
x100_b
Physical value Inp_b at 100%
Real
100
XbFail
Substitute value with sensor error at Inp_b
Real
0
Tfm_b
Filter time constant of Inp_b in seconds
Real
0,5
9499-040-82711
Modular I/O - extension-modules
U_INP (analog input card -50...1500mV, 0...10V)
III-306