Digital outputs

z1

d1, d2, d3. or d4
According to the input value of Select (or to values seld1, seld2) the relevant input variable is output.

Analog outputs

Casc

Cascade output = Select – 3.0

III-7.6

SELP ( parameter selection (No. 34))

Dependent of control signals d1 and d2, either one of the three preset parameters C1, C2, C3 or input variable x1 is
connected with output y1. Unused inputs are interpreted as 0 or logic 0.

Inputs/outputs

Digital inputs

d1

1st digital input for parameter selection

d2

2nd digital input for parameter selection

Analog input

x1

Input is output at

y1, when d1 = 1 and d2 =1

Analog outputs

d1

d2

y1 = C1

0

0

y1 = C2

0

1

y1 = C3

1

0

y1 = x1

1

1

Parameters:

Parameter

Description

Range

Default

C1

1st constant, output at y1 with

d1 = 0 and d2 = 0 .

-29 999...999 999

0

C2

2nd constant, output at y1 with

d1 = 0 and d2 = 1 .

-29 999...999 999

0

C3

3rd constant, output at y1 with

d1 = 1 and d2 = 0 .

-29 999...999 999

0

9499-040-82711

Selecting and storage

SELP ( parameter selection (No. 34))

III-138

d1
d2

x1

0 0 1

0 1 2

1 0 3

1 1 4

y1

C2

C3

C1