beautypg.com

West Control Solutions KS98-1 User Manual

Page 213

background image

Run, reset, preset and search are concerned, see following table:

Input field

Operation

Display

FB input

Header

Selection of slave block

Display of slave data

- : -

auto/manual

Operating mode selection

auto or manual

- : -

setpoint

Automatic: programmer ,
Manual mode: operator setting in input field

Active

- : -

Rec

If input

ProgNo is wired, entering of the de-

sired recipe number is not possible over the
frontside!

indicates the actual recipe number.

ProgNo

Seg

If control input

preset is wired, entering the de-

sired segmentnumber is not possible over the
frontside!

indicates the actual segment number

preset

tNetto

Entry of required programmer time (preset to time)

indicates the

run time total (with-

out pause)

preset

tRest

No operation possible

indicates the time until program end

Status

stop

Stop the programmer

programmer stopped

run

run

Start the programmer

the programmer was started

reset

The programmer is switched to segment 0
and’

stop‘

the programmer is switched to seg-
ment 0 and’

stop‘

reset

quit

Leave the field without change

program

direct adjustment of segment parameters

segmentparameter

Notes related to the properties of the operating page

The display fields shown in bold and underlined letters on the picture above mark the elements which are switched
over when changing to a slave page (see sections Master/slave operation on page 215).

The remaining fields continue indicating statuses and values of the master page.

Recipe name:

Recipes can be selected in the reset status. Unless a user text (TEXT block at ProgNo input) is provided, ‘Rec n‘ is dis-
played (n stands for the current recipe number).

• The process value is visible only with the process value input connected.
• The segment number is adjustable only with preset to segment.
• The can be adjusted only during manual mode.
• Display of the remaining segment time is suppressed with preset to segment (e.g. with digital slave

programmers).

• The program net time is adjustable with preset to time.
• 3 statuses are displayed (partly adjustable, dependent on operating status):

– Status left: automatic / manual (adjustable)

– Status middle: halt / end (unless one of the two statuses is active, this display is omitted)

– Status right: stop / run / reset / search / program / quit / error

9499-040-82711

Programmer

APROG ( analog programmer (No. 24)) / APROGD ( APROG data (No. 25))

III-213