Measured value correction 275, Parameter and configuration data, Measured value conditioning – West Control Solutions KS98-1 User Manual
Page 275
Parameter and configuration data
Parameter
Description
Values
Default
x1in
Measured value correction P1, input
-29999 ... 999 999
0
x1out
Measured value correction P1, output
-29999 ... 999 999
0
x2in
Measured value correction P2, input
-29999 ... 999 999
100
x2out
Measured value correction P2, output
-29999 ... 200000
100
Configuration Description
Values
Default
Type
Type L -200...900 °C
Type L
Type J -200...900 °C
Type J
Type K -200...1350 °C
Type K
Type N -200...1300 °C
Type N
Type S -50...1760 °C
Type S
Type R -50...1760 °C
Type R
Type T -200...400 °C
Type T
Type W 0...2300 °C
Type W
Type E -200...900 °C
Type E
Type B 0...1820 °C
Type B
Pt 100 -99,9...850,0 °C
Pt100 850
Pt 100 -99,9...250,0 °C
Pt100 250
2x Pt 100 -99,9...850 °C
2Pt100 85
2x Pt 100 -99,9...250,0 °C
2Pt100 25
0...20 mA
0...20mA
t
4...20 mA
4...20mA
0...10 V
0...10V
2...10 V
2...10V
Transducer 0...500 [
Pot.trans
Resistance 0...500 [ linear
0..500Ohm
Resistance 0...250 [ linear
0..250Ohm
Fail
Fail function off
disabled
Digital output
fail = 1, y1 = x100
Upscale
t
Digital output
fail = 1, y1 = x0
Downscale
Digital output
fail = 1, y1 = XFail
Subst.val.
Xkorr
Measured value correction off
off
t
Measured value correction adjustable
on
Unit
Unit = °C
only effective with
thermocouple and Pt100 setting
°C
t
Unit = °F
°F
STK
Internal temperature compens.
only effective with
thermocouple
int.CJC
t
External temperature compens.
ext.CJC
x0
Physical value at 0%
only effective with standard
signals (0/4..20mA or 0/2..10V)
-29999 ... 999 999
0
x100
Physical value at 100%
-29999 ... 999 999
100
XFail
Substitute value with sensor error
-29999 ... 999 999
0
Tfm
Filtertime constant
[s]
0 ... 999 999
0,5
Tkref
Reference temperature at
STK = ext.TK
0 ... 140
0
Measured value conditioning
Before the pre-filtered (time constant ...; limiting frequency ...) analog
input signals are available as digitized measurement values with
physical quantiy, they are subjected to extensive measured value
conditioning.
Inputs
9499-040-82711
III-275
AINP1 ( analog input 1 (No. 08))
y1
Unit
STK
Tkref
Typ
XFail
Fail
x0
x100
Tfm
x2out
Xkorr
x2in
x1out
x1in