Parameter for contr and contr – West Control Solutions KS98-1 User Manual
Page 226
Analog outputs:
Weff
Effective
X
Effective process value
Y
Effective output value
XW
Control deviation
W
Internal
Yout1
Output value yout1 (heating)
Yout2
Correcting variable yout2 (cooling; only with continuous controller with split-range behaviour r CFunc=
splitRange)
ParNo
Only with CONTR+; effective parameter set
Bl-no
Own block number
III-16.3
Parameter and Konfiguration for CONTR, CONTR+
Parameter for CONTR and CONTR+
Parameter
Description
Description
Default
Unit
W_BWlock
switchover
disable func-
tion
Switchover is disabled via front-panel operation
0: block All
t
Wext
i
Wint switchover is disabled
1: block We
W i W2 switchover is disabled
2; block W2
All switchover functions are enabled
3: none
W0
Min. limit (Weff)
-29999...999999
0
0
W100
Max. limit (Weff)
-29999...999999
100
100
W2
Additional setpoint
-29999...999999
100
100
Grw+
3)
Gradient plus unit/min
0,001...999999
Off
----
Grw-
3)
Gradient minus unit/min
0,001...999999
Off
----
Grw2
3)
Setpoint gradient for W2 unit/min
0,001...999999
Off
----
N0
Zero offset for ratio control
-29999...999999
0
0
a
Factor a for 3-element control + setpoint ramps
-9,99...99,99
1
1
Xsh
2)
Trigger point separation (stepping controller)
0,2...20,0%
0,2
0,2
Tpuls
Min. positioning step time (stepping controller)
0,1...2,0[s]
0,3
0,3
Tm
Actuator response time (stepping controller)
5...999999 [s]
30
30
Xsd1
Switching difference (signaller control)
0,10...999999
1
1
LW
Distance additional contact (signaller control)
-29999...999999
Off
----
Xsd2
Switching difference additional contact (signaller control)
0,10...999999
1
1
Xsh1
1)
Trigger point separation (PD) (3-point controller)
0,0...1000,0[%]
0
0
Xsh2
1)
Trigger point separation (PD) (3-point controller)
0,0...1000,0[%]
0
0
Y2
Additional correcting variable (not for stepping controllers)
-105,0...105,0[%]
0
0
Ymin
Min. correcting variable limiting (not for stepping controller)
-105,0...105,0[%]
0
0
Ymax
Max. correcting variable limiting (not for stepping controller)
-105,0...105,0[%]
100
100
Y0
Working point of the controller (not for stepping controller)
-105,0...105,0[%]
0
0
Y0ptm
4)
Positioning value during process at rest
-105,0...105,0[%]
0
0
dYopt
4)
Self tuning step height
5...100[%]
100
100
P0pt
4)
Only for CONTR+; parameter set to be optimized
1...6
1
1
Xp1 1...6
1)
Proportional band 1
0,1...999,9[%]
100
100
Xp2 1...6
1)
Proportional band 2 (three-point and split range)
0,1...999,9[%]
100
100
Tn 1...6
Integral action time
(Tn = 0 r I-part is not effective)
0,0...999999[s]
10
10
Tv 1...6
Derivative time (Tv = 0 r D-part is not effective)
0,0...999999[s]
10
10
Tp1 1...6
Cycle time heating (2-and 3-point controller)
0,4...999,9[s]
5
5
Tp2 1...6
Cycle time cooling (3-point controller)
0,4...999,9[s]
5
5
1)
%-specifications are related to measuring range x
n0
... x
n100
2)
The neutral zone x
sn
for 3-point stepping controllers depends on T
puls
, T
m
and x
p1
(r V. Hints for self-tuning).
3)
Gradient control r page 261
4)
Self optimizationr page 242 ff
Controller
9499-040-82711
III-226
Parameter and Konfiguration for CONTR, CONTR+