beautypg.com

I-6 electrical connections - safety hints 23, I-6.1 electromagnetic compatibility 23, I-6.2 measurement earth connection 23 – West Control Solutions KS98-1 User Manual

Page 23: Electrical connection 23 - 28, I-6 electrical connections - safety hints

background image

I-6

Electrical connections - Safety hints

a

Following the safety notes starting on page 6 is indispensable!

The installation must be provided with a switch or power circuit breaker which must be marked accordingly. The
switch must be located near the instrument and readily accessible for the operator.

a

When the instrument module is withdrawn from the housing, protection against dropping of conducting
parts into the open housing must be fitted.

a

The protective earth terminal (P3) must be connected to the cabinet ground. This applies also to 24V supply.

I-6.1

Electromagnetic compatibility

European guideline 89/336/EEC. The following European standards are met: EN 61326-1.

The unit can be installed in industrial areas (risk of radio interference in residential areas). A considerable increase of
the electromagnetic compatibility is possible by the following measures:

w

Installation of the unit in an earthed metal control cabinet.

w

Keeping power supply cables separate from signal and measurement cables.

w

Using twisted and screened measurement and signal cables (connect the screening to measurement earth).

w

Providing connected motor actuators with protective circuitry to manufacturer specifications. This measure pre-
vents high voltage peaks which may cause trouble for the instrument.

I-6.2

Measurement earth connection

Measurement earth connection is required for protection against interference. External interference voltages (incl. ra -
dio frequencies) may affect the perfect function of the device.

To ensure protection against interference, the measurement earth must be connected to cabinet ground.

+

Terminals A11(measurement earth) and P3 (protective earth) must be connected to cabinet ground via a short cable
(approx. 20 cm)! The protective earth conductor of the power supply cable must also be connected to this earth poten -
tial (cabinet ground).

r See also diagram on page 24

9499-040-82711

Electrical connections - Safety hints

Electromagnetic compatibility

I-23