I-6
Electrical connections - Safety hints
a
Following the safety notes starting on page 6 is indispensable!
The installation must be provided with a switch or power circuit breaker which must be marked accordingly. The
switch must be located near the instrument and readily accessible for the operator.
a
When the instrument module is withdrawn from the housing, protection against dropping of conducting
parts into the open housing must be fitted.
a
The protective earth terminal (P3) must be connected to the cabinet ground. This applies also to 24V supply.
I-6.1
Electromagnetic compatibility
European guideline 89/336/EEC. The following European standards are met: EN 61326-1.
The unit can be installed in industrial areas (risk of radio interference in residential areas). A considerable increase of
the electromagnetic compatibility is possible by the following measures:
w
Installation of the unit in an earthed metal control cabinet.
w
Keeping power supply cables separate from signal and measurement cables.
w
Using twisted and screened measurement and signal cables (connect the screening to measurement earth).
w
Providing connected motor actuators with protective circuitry to manufacturer specifications. This measure pre-
vents high voltage peaks which may cause trouble for the instrument.
I-6.2
Measurement earth connection
Measurement earth connection is required for protection against interference. External interference voltages (incl. ra -
dio frequencies) may affect the perfect function of the device.
To ensure protection against interference, the measurement earth must be connected to cabinet ground.
+
Terminals A11(measurement earth) and P3 (protective earth) must be connected to cabinet ground via a short cable
(approx. 20 cm)! The protective earth conductor of the power supply cable must also be connected to this earth poten -
tial (cabinet ground).
r See also diagram on page 24