III-20 Modular I/O - extension-modules

The modular C-Card offers the possibility, to adjust the kind and type of process in- and outputs to the plant. Despite of
following limitation, up to four modules can be fitted as desired.

Performance limits
Due to the maximum permissible self-heating

, the number of analog output modules is limited. The total of performance factors

(P-factor, r Technical data must not exceed 100%! Exceeded performance limits are displayed in the engineering tool.

Performance factor of the modules

R_INP

TC_INP

U_INP

F_INP

DIDO

U_OUT

I_OUT

= 5%

= 5%

= 8%

= 8%

= 15%

= 25%

= 70%

This means:

Max. one I_OUT-module (any socket )!
Max. one U_OUT-module, if there is already a current output module (but in different, galvanically isolated module groups)!

Example:

current output module on slot 1 or 2 and voltage output module on slot 3 or 4.
The total of P factors is 95%. I.e. 1 more resistance or 1 TC/mV/mA module can be fitted.
Galvanic isolation: Slots 1-2 are galvanically isolated from 3-4.

III-20.1

TC_INP (analog input card TC, mV, mA)

Analog input, plugs into modular options card C. The function TC_INP is used for configuration and parameter setting
of the analog inputs

TC_INP. Calculation of the inputs is fixed to once per time slot.

9499-040-82711

Modular I/O - extension-modules

TC_INP (analog input card TC, mV, mA)

III-300

Fail_a
XaFail

X0_a

X100_a

Tfm_a

Xakorr

x1a in

x1a Out

x2a in

x2a out

fail_a

Inp_a

Typ_a

Unit_a

STK_a

Tkrefa

Fail_b
XbFail

X0_b

X100_b

Tfm_b

Xbkorr

x1b in

x1b Out

x2b in

x2b out

fail_b

Inp_b

Typ_b

Unit_b

STK_b

Tkrefb

slotid