Sequence control 111, Sequencing 111, Step 111 – West Control Solutions KS98-1 User Manual
Page 111: Step function for sequencing 111, Parameters
Parameters:
Parameter Description
Range
Default
Mode 1
Source of pulse duration at
z1
Parameter Ti1
Para.Ti1
t
Input Ti1
Input Ti1
Mode 2
Source of pulse duration at
z3
Parameter Ti2
Para.Ti2
t
Input Ti2
Input Ti2
Ti1
Duration of the pulse generated by
d1,when Mode 1 = Para.Ti1 is entered.
0,1...999 999 [s]
1
Ti2
Duration of the pulse generated by
d2, when Mode 2 = Para.Ti2 is entered.
0,1...999 999 [s]
1
III-4.8
STEP (step function for sequencing (No. 68))
The STEP function realizes the individual steps for sequencing.
The function starts with RESET at step 1 and remains at this step, until the relevant condition input d
1
or the skip input
is set from 0 to 1. This is followed by switch-over to step 2. The procedure for all further steps is identical.
The step number is output as a value at output Step.
Example:
Switch-over from step 3 (
Step = 3) to step 4 (Step = 4) is only after the condition at d3 was met (d3 = 1). The con-
dition at
d4 is checked only when calling up the function for the next time. Thus immediate switch-over is prevented. As
long as
d3 = 0, the value of output Step remains 3.
Alternatively, a positive flank at input
skip also leads to switch-over to the next step (independent of the status at
input
d1..d10).
a
The function has a ‘memory’. This means: after power-on, it continues operating with the step at
power-off, provided that the RAM data are still unchanged.
When several switch-over conditions are 1 simultaneously (e.g.
d1, d2, d3, d4 and d5), only the instantaneously
effective input is handled. I.e. in each calculation cycle, switch-over is only by one step. For realizing a sequencing with
more than 10 steps, the STEP function can be cascaded:
The wiring example shows how 2 STEP functions are cascaded. With cascading, step number 1...n is output always as
a value at output
Step of the last follow-up step.
For resetting the cascaded stepping control, reset wiring at the 1st function block is required.
Logic functions
9499-040-82711
III-111
STEP (step function for sequencing (No. 68))
reset
stop
skip
Casc
activ
Step
d1
d10
...
STEP