With a positive edge at the
store input, the values applied to the signal inputs are stored as parameters y1
and
y2, i.e. as output values.
w
When an ALLP is connected at inputs x1 and x2, its limits L1 and H1 are used for parameter adjustment.
With digital input
lock set, no values can be changed. With digital input hide set, the operating page cannot be
displayed during operation. A 16-digit text for the display header can be adjusted user-specifically via the engineering
tool. The same is applicable for further texts for identification of value and unit.
a
Values of the used analog inputs are stored as parameter values when detecting a positive edge at the
store- input. This input should be activated only with relevant changes of the input values. Too frequent
storing operations may lead to the destruction of the EEPROM! (
r page 311)
Inputs/outputs
Digital inputs:
hide
Display suppression (with
hide = 1 the operating page is not displayed).
lock
Adjustment blocking (with
lock = 1 these values cannot be adjusted by means of keys ID).
Analog inputs:
x1 / x2
Process values to be displayed as values (default = 0)
x3 / x4
Process values to be displayed as bargraph (default = 0)
Analog outputs:
y1 / y2
Valid process values
Parameter and configuration data
Parameter
Description
Range
Default
Y1 / Y2
Start values at power-on
-29999...999 999
0
Configuration Description
Values
Default
Disp1
Disp2
Function of
numeric
display 1 and
2
display x1 / x2, value adjustable
disp+adj
only display x1 / x2
display
t
x1 / x2 = empty
empty
Dp1 / Dp2
Digits behind the decimal point in numeric display 1 / 2
0 ... 3
0
Typ
Position of
bargraphs
Both bargraphs horizontal
horizont
t
Both bargraphs vertical
vertical
X3
0
Display scaling bargraph 1, 0% (left or bottom end)
-29999...999 999
0
X3 100
Display scaling bargraph 1, 100% (right or upper end)
-29999...999 999
100
X3 mid
Display scaling bargraph 1, start value (middle)
-29999...999 999
0
X4
0
Display scaling bargraph 2, 0% (left or bottom end)
-29999...999 999
0
X4 100
Display scaling bargraph 2, 100% (right or upper end)
-29999...999 999
100
X4 mid
Display scaling bargraph 2, start value (middle)
-29999...999 999
0
9499-040-82711
Visualization
VBAR ( bargraph display (No. 97) )