beautypg.com

Iii-18.2 out3 ( process output 3 (no. 118)) 287, Out3 287, Process output 3 287 – West Control Solutions KS98-1 User Manual

Page 287

background image

III-18.2

OUT3 ( process output 3 (No. 118))

Function OUT3 is used for process output OUT3 configuration and parameter setting.

This analog output is provided only with hardware option C.

The function is firmly allocated to block number 83, it is calculated invariably in each time slot.

With digital input

d1 used as signal source, it is switched over between 0 and 20mA as a output.

Analog input

x1 used as signal source is taken to the continuous output linearly between x0 and x100 according

to configuration.

Inputs / outputs

Digital input:
d1

Input signal with digital signal conversion

Analog input:
x1

Input signal with analog signal conversion

Configuration parameters:

Parameter

Description

Values

Default

Src

Signal source

Digital input

d1

Digital

Analog input

x1

Analog

t

Mode

Signal source action

direct/normally open

direct

t

inverse/normally closed

inverse

Type

Continuous output function

logic 0/20 mA

logic

0...20mA

0...20mA

t

4...20mA

4...20mA

x0

Analog input value

x1 at 0%

-29 999 ... 999 999

0

x100

Analog input value

x1 at 100%

-29 999 ... 999 999

100

Outputs

9499-040-82711

III-287

OUT3 ( process output 3 (No. 118))

HARDW

ARE

SOFTW

ARE

Logik
0..20mA
4...20mA

d1
x1

OUT3

Src

x0

x100

Type

Mode