Iii-18.2 out3 ( process output 3 (no. 118)) 287, Out3 287, Process output 3 287 – West Control Solutions KS98-1 User Manual
Page 287
III-18.2
OUT3 ( process output 3 (No. 118))
Function OUT3 is used for process output OUT3 configuration and parameter setting.
This analog output is provided only with hardware option C.
The function is firmly allocated to block number 83, it is calculated invariably in each time slot.
With digital input
d1 used as signal source, it is switched over between 0 and 20mA as a output.
Analog input
x1 used as signal source is taken to the continuous output linearly between x0 and x100 according
to configuration.
Inputs / outputs
Digital input:
d1
Input signal with digital signal conversion
Analog input:
x1
Input signal with analog signal conversion
Configuration parameters:
Parameter
Description
Values
Default
Src
Signal source
Digital input
d1
Digital
Analog input
x1
Analog
t
Mode
Signal source action
direct/normally open
direct
t
inverse/normally closed
inverse
Type
Continuous output function
logic 0/20 mA
logic
0...20mA
0...20mA
t
4...20mA
4...20mA
x0
Analog input value
x1 at 0%
-29 999 ... 999 999
0
x100
Analog input value
x1 at 100%
-29 999 ... 999 999
100
Outputs
9499-040-82711
III-287
OUT3 ( process output 3 (No. 118))
HARDW
ARE
SOFTW
ARE
Logik
0..20mA
4...20mA
d1
x1
OUT3
Src
x0
x100
Type
Mode