Inputs/outputs, Parameter – West Control Solutions KS98-1 User Manual

Page 144

background image

In this example, CONST output y16 = 0 is set.

The following formulas are calculated:

The left 2OF3:

x

x

x

y

1 1

2 1

3 0

2

1

Ч + Ч + Ч

=

and the right 2OF3:

x

x

x

y

1 1

2 1

3 2

4

1

Ч + Ч + Ч

=

Inputs/outputs

Digital inputs

fail1

Error message for input

x1. With fail1 = 1, input x1 is not taken into account for mean value formation.

fail2

Error message for input

x2. With fail2 = 1, input x2 is not taken into account for mean value formation.

fail3

Error message for input

x3. With fail3 = 1, input x3 is not taken into account for mean value formation.

off

Function switch-off: with

off = 1, input x1 is output at y1.

Analog inputs

x1

Measurement input 1

x1mult

Factor input, pertaining to measurement input 1. Determination is made of how many measurement inputs the

x1

consists (required with function block cascading or input

x1

not connected).

Non-connected input

x1mult is evaluated as value 1.

x2

Measuring input 2

x2mult

Factor input, pertains to measurement input 2. Determination is made of how many measurement inputs the

x2

consists (required with function block cascading or input

x2 not connected ).

Non-connected input

x2mult is evaluated as value 1.

x3

Measurement input 3

x3mult

Factor input, pertains to measurement input 3. Determination is made of how many measurement inputs

x3 con-

sists (required with function block cascading or input

x3 not connected).

Non-connected input

x3mult is evaluated as value 1.

Digital outputs

err1

Error message:

err1 = 1 indicates that at least one of inputs x1... x3 is not taken into account with mean

value formation.

err2

Error message:

err2 = 1 indicates that mean value formation is omitted. Either several inputs (fail or differ-

ence >

Diff) are disturbed or function was switched off by input off.

Analog outputs

y1

arithmetic mean value or switching to

x1 occurred ( off= 1 or several inputs defective).

Casc

Factor: number of the values used for mean value formation.
Casc = x1mult + x2mult + x3mult.

Parameter

:

Parameter Description

Range

Default

Diff

Limit value for comparison of differences between inputs
x1 ... x3 for determination of faulty inputs.

0...999 999

1

No configuration parameters!

9499-040-82711

Selecting and storage

2OF3 ( 2-out-of-3 selection with mean value formation (No. 38))

III-144