Inputs/outputs, Parameter – West Control Solutions KS98-1 User Manual
Page 144
In this example, CONST output y16 = 0 is set.
The following formulas are calculated:
The left 2OF3:
x
x
x
y
1 1
2 1
3 0
2
1
Ч + Ч + Ч
=
and the right 2OF3:
x
x
x
y
1 1
2 1
3 2
4
1
Ч + Ч + Ч
=
Inputs/outputs
Digital inputs
fail1
Error message for input
x1. With fail1 = 1, input x1 is not taken into account for mean value formation.
fail2
Error message for input
x2. With fail2 = 1, input x2 is not taken into account for mean value formation.
fail3
Error message for input
x3. With fail3 = 1, input x3 is not taken into account for mean value formation.
off
Function switch-off: with
off = 1, input x1 is output at y1.
Analog inputs
x1
Measurement input 1
x1mult
Factor input, pertaining to measurement input 1. Determination is made of how many measurement inputs the
x1
consists (required with function block cascading or input
x1
not connected).
Non-connected input
x1mult is evaluated as value 1.
x2
Measuring input 2
x2mult
Factor input, pertains to measurement input 2. Determination is made of how many measurement inputs the
x2
consists (required with function block cascading or input
x2 not connected ).
Non-connected input
x2mult is evaluated as value 1.
x3
Measurement input 3
x3mult
Factor input, pertains to measurement input 3. Determination is made of how many measurement inputs
x3 con-
sists (required with function block cascading or input
x3 not connected).
Non-connected input
x3mult is evaluated as value 1.
Digital outputs
err1
Error message:
err1 = 1 indicates that at least one of inputs x1... x3 is not taken into account with mean
value formation.
err2
Error message:
err2 = 1 indicates that mean value formation is omitted. Either several inputs (fail or differ-
ence >
Diff) are disturbed or function was switched off by input off.
Analog outputs
y1
arithmetic mean value or switching to
x1 occurred ( off= 1 or several inputs defective).
Casc
Factor: number of the values used for mean value formation.
Casc = x1mult + x2mult + x3mult.
Parameter
:
Parameter Description
Range
Default
Diff
Limit value for comparison of differences between inputs
x1 ... x3 for determination of faulty inputs.
0...999 999
1
No configuration parameters!
9499-040-82711
Selecting and storage
2OF3 ( 2-out-of-3 selection with mean value formation (No. 38))
III-144