Inputs/outputs, Parameter and configuration data – West Control Solutions KS98-1 User Manual
Page 220
Inputs/outputs
Digital inputs (DPROG):
hide
Display suppression (with
hide = 1 the page is not displayed in the operation).
lock
Adjustment blocking (with
lock = 1 the values are not adjustable by means of keys ID).
run
Program stop/run ( 0 = stop, 1 = run )
reset has highest priority
reset
Program continue/reset (0 = continue, 1 = reset )
preset
Program preset ( 1 = preset )
search
Start programm search run (1 = search )
p-show
Program editing enabled
halt
Program interruption (e.g. due to an exceeded bandwidth detected outside the programmer).
0 = program not halted
1 = program halted
manfree
Manual mode disabled
0 = switchover to manual mode not permitted
1 = switchover to manual mode is permitted
Digital outputs (DPROG):
run
Status program stop/run (0 = program stop ; 1 = program run)
reset
Status program reset (1 = program reset)
end
Status program end (1 = program end reached)
fkey
Status H key / interface function `fkey’ (:pressing key H causes switch-over (0 or 1))
do1... do6
status of control outputs in the actual segment
preset
This output indicates a programmer preset operation. With a single preset command, a pulse is output for
the duration of one cycle (dependent on the time slot in which the programmer is classified). If the program-
mer is held in preset continuously, this output is always active.
0 = no preset status
1 = APROG stands in preset status
manual
This output indicates the progrmmer manual mode.
0 = APROG works in automatic mode
1 = APROG works in manual mode
Analog inputs (DPROG):
PSet
Preset value for program
DBlock
Block number of 1st data function `APROGD’
ProgNo
Required program number (recipe)
SlavNo
SlavNo: Block number of a connected slave block (for coupling master and slave blocks (APROG or DPROG)
Analog inputs (DPROGD):
DBlock
Block number of cascadable data function `DPROGD’
Analog outputs (DPROG):
TNetto
Net program time ( ] Trun)
TBrutt
Gross program time (] Trun + ] Tstop)
TRest
Programmer rest time
SegNo
Actual segment number
ProgNo
Actual program number (recipe)
SegRest
Remaining segment time
Bl-no
Own block-number (e.g. for coupling master and slave blocks)
Analog outputs (DPROGD):
DBlock
Own block number
Parameter and configuration data
Parameter
DPROG
Description
Range
Default
PMode
Preset Mode:
Preset to segment
Pres.time
t
Preset to time
Pres.seg.
RecMax
Max.recipees
1..99
99
D0
Status of control outputs 6...1 with reset
0 / 1 per output
000000
Programmer
9499-040-82711
III-220