Iii-6.7 timer ( timer (no. 67) ) 132, Iii-6.7 timer ( timer (no. 67) ) – West Control Solutions KS98-1 User Manual
Page 132
III-6.7
TIMER ( timer (No. 67) )
The function timer can only be used with real-time clock (9407-9xx-2xxx). Output
z
1
is switched on at absolute time
TS and switched off again after TE. This switching operation can be unique or cyclical (parameter adjustment). Out-
put
Week-D indicates the actual weekday (0...6 = Su...Sa) . TS.Mo = 0 and TS.D = 0 means actual day
When the time defined with
TS.H and TS:Mi has elapsed, the 1st switching operation occurs on the following
day. With
TS.Mo = 0 and TS.D < actual day, the first switching operation occurs in the following month. With
TS.Mo ß actual month and TS.D < actual day, the 1st switching operation occurs in the next year.
Inputs/outputs
Digital input
disabl
= 0 output z1 active. Becomes 1 when the time was reached.
disabl
= 1 output z1 switched off. The output behaves like “time not yet reached”.
Digital output
z1
z1 is logic 1 between the start and end time.
Analog output
Week-D
indicates the actual weekday ( 0...6 = Su...Sa)
Parameters:
Parameter
Description
Range
Default
TS.Mo
Switch-on time month
0...12
0
TS.D
Switch-on time day
0...31
0
TS.H
Switch-on time hour
0...23
0
TS.Mi
Switch-on time minute
0...59
0
TE.D
Time duration days
0...255
0
TE.H
Time duration hours
0...23
0
TE.Mi
Time duration minutes
0...29
0
Configuration:
Configuration
Description
Value
Default
Func1
cyclical function runs cyclically
0
0
once function runs once
1
Func2
daily function runs daily
0
0
Mo...Fr. Function runs from Monday to Friday
1
Mo... Sa.function runs from Monday to Saturday
2
weekly function runs weekly
3
* 1) with the engineering tool broken rational numbers can be used; however only the integral portion is taken over!
9499-040-82711
Time functions
TIMER ( timer (No. 67) )
III-132