beautypg.com

Iii-6.7 timer ( timer (no. 67) ) 132, Iii-6.7 timer ( timer (no. 67) ) – West Control Solutions KS98-1 User Manual

Page 132

background image

III-6.7

TIMER ( timer (No. 67) )

The function timer can only be used with real-time clock (9407-9xx-2xxx). Output

z

1

is switched on at absolute time

TS and switched off again after TE. This switching operation can be unique or cyclical (parameter adjustment). Out-
put

Week-D indicates the actual weekday (0...6 = Su...Sa) . TS.Mo = 0 and TS.D = 0 means actual day

When the time defined with

TS.H and TS:Mi has elapsed, the 1st switching operation occurs on the following

day. With

TS.Mo = 0 and TS.D < actual day, the first switching operation occurs in the following month. With

TS.Mo ß actual month and TS.D < actual day, the 1st switching operation occurs in the next year.

Inputs/outputs

Digital input
disabl

= 0 output z1 active. Becomes 1 when the time was reached.

disabl

= 1 output z1 switched off. The output behaves like “time not yet reached”.

Digital output
z1

z1 is logic 1 between the start and end time.

Analog output
Week-D

indicates the actual weekday ( 0...6 = Su...Sa)

Parameters:

Parameter

Description

Range

Default

TS.Mo

Switch-on time month

0...12

0

TS.D

Switch-on time day

0...31

0

TS.H

Switch-on time hour

0...23

0

TS.Mi

Switch-on time minute

0...59

0

TE.D

Time duration days

0...255

0

TE.H

Time duration hours

0...23

0

TE.Mi

Time duration minutes

0...29

0

Configuration:

Configuration

Description

Value

Default

Func1

cyclical function runs cyclically

0

0

once function runs once

1

Func2

daily function runs daily

0

0

Mo...Fr. Function runs from Monday to Friday

1

Mo... Sa.function runs from Monday to Saturday

2

weekly function runs weekly

3

* 1) with the engineering tool broken rational numbers can be used; however only the integral portion is taken over!

9499-040-82711

Time functions

TIMER ( timer (No. 67) )

III-132