beautypg.com

Iii-5.5 coun (up/down counter (no. 74)) 120, Coun 120, Counter 120 – West Control Solutions KS98-1 User Manual

Page 120: Down/up counter 120, Up/down counter 120, Iii-5.5 coun (up/down counter (no. 74))

background image

III-5.5

COUN (up/down counter (No. 74))

‘COUN’ is an up/down counter and counts the events at input up or down, which are available at the up or down input
for at least the duration of the time group in which the function runs.

reset

preset

Mode

0

0

GO (default)

0

1

Preset

1

0

Reset (first run)

1

1

Reset (first run)

Example: max. limit = 9; min. limit = 0; Preset = 7.
An unwired clock input is set to value 1 internally. If both clock inputs go from 0 to 1 signal simultaneously, counting is
omitted. If one of clock inputs (up or down) are set from 0 to 1 signal, without the other one being already set to 1,
counting is omitted.

If parameters for the min. or max. limit are changed during operation, the counter can be out of this new range. In or -
der to prevent faulty functions, the counter must be set to a new, defined output status with ‘reset’ or ‘preset’. The
function has a ‘memory’. This means: after power-on, it continues operating with counter state and internal states at
power-off, provided that the RAM data are still unchanged.

9499-040-82711

Signal converters

COUN (up/down counter (No. 74))

III-120

>Tr

>Tr

reset
preset

Preset

down
up

Count

carry

borrow

&

&

&

y0

Mode

Min

0000

Max

9999

reset

Preset

up

down

carry

borrow

Count

0

7

8

9

0

1

2

1

0

9

8

7

Fig. 3 Pulse diagram of the up/down counter:

"up,down, carry und borrow" sind in inaktivem Zustand 1.