III-17.3
AINP6 ( analog input 6 (No. 115))
For direct connection of potentiometric transducer and standard signal
General
Function ‘AINP6’ is used for configuration and parameter setting of analog input INP6. It is firmly allocated to block
number 66 and is calculated in each time slot. The function provides a corrected measurement value and a measured
value status signal at its outputs.
Inputs / outputs
Digital inputs:
lock
Calibration disabled (with
lock
= 1 calibration is disabled)
hide
Display suppression (with
hide
= 1 the calibration page is disabled)
Digital outputs:
fail
Signals an input error (short circuit, wrong polarity, ..)
a/m
Manual signal
inc
Increment signal
dec
Decrement signal
Analog inputs:
Y
Output variable
Analog outputs:
Inp1
Signal input
Parameter and configuration data
Parameter
Description
Values
Default
x1in
Measured value correction P1, input
-29999 ... 999 999
0
x1out
Measured value correction P1, output
-29999 ... 999 999
0
x2in
Measured value correction P2, input
-29999 ... 999 999
100
x2out
Measured value correction P2, output
-29999 ... 999 999
100
9499-040-82711
Inputs
AINP6 ( analog input 6 (No. 115))
III-282
Typ
XFail
Fail
x0
x100
Tfm
x2out
Xkorr
x2in
x1out
x1in
Y
lock
hide
dec
inc
hand
fail
Cal
Y1