beautypg.com

Inputs/outputs, Parameters – West Control Solutions KS98-1 User Manual

Page 119

background image

Inputs/outputs

Analog input

X1

Input variable to be converted

Digital output

z1

Pulse output

No configuration parameters

Parameters:

Parameter

Description

Range

Default

x0

Span start (0 %)

-29 999...999 999

0

x100

Span end

(100 %)

-29 999...999 999

1

Puls/h

Number of output pulses per hour for x1 ? x100.

0...18 000

Equation for calculating the momentary impulse number of n per hour

n

Puls h

x

x

x

x

=

×

-

-

/

1

0

100

0

n

=

momentary impulse number/hour

x0

=

Parameter. With analog input x1 ß x0 no pulses are produced (area start,
creeping flow suppression)

x100

=

If the analog input is x1 ß x100 n remains = constant = Puls/h

Puls/h

=

Parameter. Pulse number/hour for analog input x

1

= x

100

Signal converters

9499-040-82711

III-119

PULS (analog pulse conversion (No. 73))

x1

n

x0=3

x100=100

Puls/h

0

n=3600

x1-3

100-3

=3600

Fig. 2
Example:
x1 = 3...100% = 0...3600/h
x

0

= 3

x

100

= 100

Puls/h = 3600