beautypg.com

Aprogd2 – West Control Solutions KS98-1 User Manual

Page 204

background image

APROGD2

Analog inputs (APROGD2):
DBlock

Block number of cascaded data function `APROGD’

Analog outputs (APROGD2):
DBlock

Own block number

Parameter
APROGD2

Description

Value Range

Default

ET

Unit

ET Unit

Type 1

(Type for segment 1)

0

Time segment

t

t

1

Gradient segment

2

Haltesegment

3

Sprungsegment

4

Time segment and wait at the end

5

Gradient segment and wait at the end

6

Hold segment and wait at the end

7

Step change segment and wait at the end

Typ10

Type for segment 10

like type 1

0 .. 7

...

TpGr1

Time or gradient for segment 1

0 ... 59,999

0 ... 999:59

OFF —:—

Wp1

Final value for segment 1

-29999 ... 999999

-29999 ... 999999

0

.. .

TpGr10

Time or gradient for segment 10

0...59,999

0 ... 999:59

OFF —:—

Wp10

Final value for segment 10

-29999 ... 999999

-29999 ... 999999

0

0

Configuration
APROGD2

Description

Value

PwrUp

Behaviour after mains
recovery

Continue program (default)

Prog.Fort

Search run in the actual segment

Fort.Seg.

Continue at actual time

Fort.Zeit

PEnd

Behaviour at program
end PEnd:
0 = Stop

1 = Reset
2 = Reset + Stop

(End-condition is reset

with stop)

stop after program end (default)

Stop

Reset after program end

Reset

Turbo

Time unit

Time = hours : minutes (default)

Std:Min

Time = minutes : seconds

Min:Sek

FKey

FKey (H key function):
0 = fkey output status switchover by H key (previous function)
1 = H key used to generate a pulse at the fkey output (pulse length = 1 cycle)
2 = H key controls the programmer (fkey output generates a pulse when
actuating the key, pulse length = 1 cycle)

Programmer

9499-040-82711

III-204

APROG ( analog programmer (No. 24)) / APROGD ( APROG data (No. 25))