West Control Solutions KS98-1 User Manual
Page 157
tool can be used to configure a 16-digit text for the display header and further texts for identification of value and unit,
or for the two digital statuses.
a
Values of the used analog inputs are stored as parameter values when detecting a positive edge at the
store- input. This input should be activated only with relevant changes of the input values. Too frequent
storing operations may lead to the destruction of the EEPROM! (
r page 311)
Inputs/outputs
Digital inputs:
hide
Display suppression (with
hide = 1 the page is not displayed in the operation.
lock
Adjustment locking (with
lock = 1 the values are not adjustable by means of keys ID).
d1 ... d6
Process statuses to be displayed. (Default = 0)
store
With a positive flank (0r1) the input values are used as output values.
Digital outputs:
z1 ... z6
Valid process values
change
If a value is changed during operation, the change-output of the VWERT-block is set to 1 for one calculating
cycle.
Analog inputs:
x1 ... x6
Process values to be displayed (default = 0)
casc
By wiring the casc-input with the bl-no output of another VWERT, cascades can be set up
Analog outputs:
y1 ... y6
Valid process values
Bl-no
Block number of this output
line
If a value is changed during operation, for one calculating cycle the line-output of the VWERT-block is set to
that value that was changed (1-6) .
Parameter and configuration data
Parameter
Description
Range
Default
z1 ... z6
Start values for digital outputs 1...6 at power-on
0 / 1
0
Y1 ... Y6
Start values for the analog outputs 1...6 at power on
-29999...999 999
0
Configuration Description
Values
Default
Disp1 ...
Disp6
Function of
display line 1...6
display line, value ajustable
adjustable
only display line
display
t
line = empty line
empty
Mode1 ...
Mode6
Type of display
line 1...6
analog value display
analog
t
digital value display
digital
value display in time format
time
selection group (radio button)
radio
toggle function
switch
push-button function (pressed =1)
push-button
text selection
text
menu function (page changing)
menu
Dp1 ... Dp6
Digits behind decimal point in analog line 1...6
0 ... 3
0
Visualization
9499-040-82711
III-157
VWERT ( display / definition of process values (No. 96) )