beautypg.com

West Control Solutions KS98-1 User Manual

Page 157

background image

tool can be used to configure a 16-digit text for the display header and further texts for identification of value and unit,
or for the two digital statuses.

a

Values of the used analog inputs are stored as parameter values when detecting a positive edge at the
store- input. This input should be activated only with relevant changes of the input values. Too frequent
storing operations may lead to the destruction of the EEPROM! (

r page 311)

Inputs/outputs

Digital inputs:
hide

Display suppression (with

hide = 1 the page is not displayed in the operation.

lock

Adjustment locking (with

lock = 1 the values are not adjustable by means of keys ID).

d1 ... d6

Process statuses to be displayed. (Default = 0)

store

With a positive flank (0r1) the input values are used as output values.

Digital outputs:
z1 ... z6

Valid process values

change

If a value is changed during operation, the change-output of the VWERT-block is set to 1 for one calculating
cycle.

Analog inputs:
x1 ... x6

Process values to be displayed (default = 0)

casc

By wiring the casc-input with the bl-no output of another VWERT, cascades can be set up

Analog outputs:
y1 ... y6

Valid process values

Bl-no

Block number of this output

line

If a value is changed during operation, for one calculating cycle the line-output of the VWERT-block is set to
that value that was changed (1-6) .

Parameter and configuration data

Parameter

Description

Range

Default

z1 ... z6

Start values for digital outputs 1...6 at power-on

0 / 1

0

Y1 ... Y6

Start values for the analog outputs 1...6 at power on

-29999...999 999

0

Configuration Description

Values

Default

Disp1 ...
Disp6

Function of

display line 1...6

display line, value ajustable

adjustable

only display line

display

t

line = empty line

empty

Mode1 ...
Mode6

Type of display

line 1...6

analog value display

analog

t

digital value display

digital

value display in time format

time

selection group (radio button)

radio

toggle function

switch

push-button function (pressed =1)

push-button

text selection

text

menu function (page changing)

menu

Dp1 ... Dp6

Digits behind decimal point in analog line 1...6

0 ... 3

0

Visualization

9499-040-82711

III-157