Iii-5 signal converters 114, Iii-5.1 aoctet (data type conversion (no. 02)) 114, Aoctet 114 – West Control Solutions KS98-1 User Manual
Page 114: Data type conversion 114, Iii-5 signal converters, Iii-5.1 aoctet (data type conversion (no. 02))
III-5
Signal converters
III-5.1
AOCTET (data type conversion (No. 02))
Function AOCTET converts an analog value (X1) into the individual bytes (Ooct1-4) of a data type as used e.g. for trans -
mission via the CAN bus ( see CPREAD / CPWRIT ). In the CAN notation, the bytes are transmitted in Intel format. Un -
less connected instruments are in compliance with this notation, word or bytewise echange of the bytes may be
necessary.
The function works in both directions simultaneously ( analog > bytes / bytes > analog ) with separate data type adjust -
ment in the parameters.
Analog inputs:
X1
analog input value
Ioct1..4
analog input byte value 1
Analog outputs:
Y 1
analog output value
Ioct1..4
analog output byte value 1
Parameters:
Parameter
Description
Value range
Default
Ioct
data type of analog > byte conversion
0...999 999 [s]
0
Ooct
data type of byte > analog conversion
The following data types are available
0
1
2
3
4
5
6
Uint8
Int8
Uint16
Int16
Uint32
Int32
Float
9499-040-82711
Signal converters
AOCTET (data type conversion (No. 02))
III-114