Iii-18 outputs 286, Out1 and out2 286, Outputs 286 – West Control Solutions KS98-1 User Manual
Page 286: Process outputs 1 and 2 286, Iii-18 outputs
III-18 Outputs
III-18.1
OUT1 and OUT2 ( process outputs 1 and 2 (No. 116, 117))
Functions OUT1 and OUT2 are used for process output OUT1 and OUT2 configuration and parameter setting. Depend-
ent of hardware, the outputs can be analog or relay outputs. Function OUT1 is firmly allocated to block number 81,
function OUT2 is firmly allocated to block number 82. They are calculated invariably in each time slot.
With digital input
d1 used as signal source, it is switched to the digital output as specified in Mode on an instru-
ment with relay output. With continuous output, switch-over is between 0 and 20 mA as with a logic output.
Analog input
x1 used as signal source is taken to the continuous output linearly between x0 and x100 dependent
of configuration. With switching output (relay or logic), switching from
x0 to x100 is from 50% (hysteresis = 1%).
Inputs / outputs
Digital input:
d1
Input signal with digital signal conversion
Analog input:
x1
Input signal with analog signal conversion
Configuration parameters:
Parameter
Description
Values
Default
Src
Signal source
Digital input
d1
Digital
t
Analog input
x1
Analog
Mode
Signal source action
direct/normally open
direct
t
inverse/normally closed
inverse
Type
Function of the continuous output
logic 0/20 mA
logic
0...20mA
0...20mA
t
4...20mA
4...20mA
x0
Analog input value
x1 at 0%
-29 999 ... 999 999
0
x100
Analog input value
x1 at 100%
-29 999 ... 999 999
100
9499-040-82711
Outputs
OUT1 and OUT2 ( process outputs 1 and 2 (No. 116, 117))
III-286
HARDW
ARE
SOFTW
ARE
Relais
Logik
0..20mA
4...20mA
d1
x1
OUT1
OUT2
OUT1
OUT2
Src
x0
x100
Type
Mode