III-20.2
F_Inp (frequency/counter input)
The frequency/counter input plugs into the modular options card C.The F_INP is used for configuration and parameter
setting of input
F_INP. Input calculation is fixed to once per time slot.
Digital inputs:
reset a
1 = the value for
Inp_a is reset to 0.
stop a
1 = the instantaneous value for
Inp_a remains unchanged.
reset b
1 = the value for
Inp_b is reset to 0.
stop b
1 = the instantaneous value for
Inp_b remains unchanged.
Digital outputs:
slotid
0 = correct module fitted
1 = wrong module fitted
fail
1 = inserted module is detected, but no communication to the module.
z_a
signal status of HW input a
z_b
signal status of HW input b
ov_a
1 = frequency at HW input a exceeds the maximum permissible 20kHz
ov_b
1 = frequency at HW input b exceeds the maximum permissible 20kHz
Analog outputs
Inp_a
output value for channel a
Inp_b
output value for channel b
Configuration
Description
Values
Default
Func_a
DigInputr con-trol input
0
1
Count_1 r up counter
1
Count_2
r up/down counter
2
Count_3
r up/down counter with direction signal
3
Count_4
r quadrature signal
4
Frequenzr fre-quency measuring
5
Func_b
DigInputr con-trol input
0
1
Count_1
r up counter
1
Frequenz
r frequency measuring
5
Time
for frequency measuring in seconds
0,1...20
10
9499-040-82711
Modular I/O - extension-modules
F_Inp (frequency/counter input)
III-302
stop a
0000
reseta
Inp_a
stop b
0000
resetb
Inp_b
a
b