Iii-8.5 limit ( multiple alarm (no. 44)) 152, Limit 152, Multiple alarm 152 – West Control Solutions KS98-1 User Manual
Page 152: Iii-8.5 limit ( multiple alarm (no. 44))
III-8.5
LIMIT ( multiple alarm (No. 44))
The function checks input variable x1 for 8 alarm values
L1...L 8. Dependent of configuration by Mode 1 ...
Mode 8, the relevant alarm value is evaluated as MAX or MIN alarm.
With MAX alarm configuration, the alarm is triggered when the input signal is higher than the alarm value and finished
when it is lower than ( alarm value - hysteresis
Xsd ).
With MIN alarm configuration, the alarm is triggered when the input signal is lower than the alarm value and finished
when it is higher than ( alarm value + hysteresis
Xsd ).
Inputs/outputs
Analog input
x1
Input variable to be monitored
Digital outputs
l1 ... l8
The alarm statuses of alarm 1 to alarm 8: 0 = no alarm; 1= alarm case
Configuration parameters:
Parameter
Description
Range
Default
Mode1 ... Mode8
alarm functions of the 8 alarms
max-alarm
MAX-alarm
t
min-alarm
MIN-alarm
Parameters:
Parameter Description
Range
Default
L1 ... L8
Alarm values of alarm 1 to alarm 8
-29 999 ... 999 999
0
Xsd
Switching hysteresis Xsd
0 ... 999 999
0
9499-040-82711
Limit value signalling and limiting
LIMIT ( multiple alarm (No. 44))
III-152
x1
L2
L8
L1
...
Mode1Mode2
Mode8
...
l1
...
l8
Xsd
Fig. 15