beautypg.com

Iii-8.5 limit ( multiple alarm (no. 44)) 152, Limit 152, Multiple alarm 152 – West Control Solutions KS98-1 User Manual

Page 152: Iii-8.5 limit ( multiple alarm (no. 44))

background image

III-8.5

LIMIT ( multiple alarm (No. 44))

The function checks input variable x1 for 8 alarm values

L1...L 8. Dependent of configuration by Mode 1 ...

Mode 8, the relevant alarm value is evaluated as MAX or MIN alarm.

With MAX alarm configuration, the alarm is triggered when the input signal is higher than the alarm value and finished
when it is lower than ( alarm value - hysteresis

Xsd ).

With MIN alarm configuration, the alarm is triggered when the input signal is lower than the alarm value and finished
when it is higher than ( alarm value + hysteresis

Xsd ).

Inputs/outputs

Analog input

x1

Input variable to be monitored

Digital outputs

l1 ... l8

The alarm statuses of alarm 1 to alarm 8: 0 = no alarm; 1= alarm case

Configuration parameters:

Parameter

Description

Range

Default

Mode1 ... Mode8

alarm functions of the 8 alarms

max-alarm

MAX-alarm

t

min-alarm

MIN-alarm

Parameters:

Parameter Description

Range

Default

L1 ... L8

Alarm values of alarm 1 to alarm 8

-29 999 ... 999 999

0

Xsd

Switching hysteresis Xsd

0 ... 999 999

0

9499-040-82711

Limit value signalling and limiting

LIMIT ( multiple alarm (No. 44))

III-152

x1

L2

L8

L1

...

Mode1Mode2

Mode8

...

l1

...

l8

Xsd

Fig. 15