Scrollin g – West Control Solutions KS98-1 User Manual
Page 214
Direct programmer adjustment
Program s and segment times can be adjusted at the operating page di -
rectly via the instrument front panel, without calling up the parameter le -
vel. Direct access to parameter setting is enabled with control input
p-show = „1" set at the function blocks of programmer APROG and
DPROG.
Menu item
Program can be selected in the status line. After confir-
mation, all segment parameters
Tp and Wp pertaining to an effective re-
cipe
Rec can be displayed and adjusted in a scroll window (Fig. ). Return
to the normal operation is with
End.
Scrolling is done over several data blocks (APROGD, APROGD2, DPROGD).
„n" segment parameter (Wpn, Tn) indexing is with 3 digits. The segment
parameters are distributed to the concerned data blocks automatically
from left to right with ascending index (Fig. ).
If the last segment time Tn is adjusted to a valid value, the next parameter
Tn+1 is displayed automatically. =
--:-- etc.
Thus an actual program can also be reduced by setting Tn+1. =
--:--
in the required position. The following segments are suppressed in the
program sequence.
However, the relevant segment parameters remain unchanged and are
made effective again by entry of a valid value at the relevant point (Fig.
45).
See chapter
r page 38
The programmer adjustment via the main menu parameter level remains
possible. In this case, however, each data block APROGD, APRGD2 or
DPROGD must be selected separately. But parameters
W0, W100 (ad-
justment limits)
and Dp (decimal points) which pertain to the APROG are not effective when entering.
Recipe names used via text blocks are displayed also on the editing page. By changing the recipe name, switching
over to the display of another recipe is possible. This can be done at any time and does not cause changing of the acti -
ve recipe.
When using APRGD2 blocks, the follo-
wing editing page is displayed.
Programmer
9499-040-82711
III-214
APROG ( analog programmer (No. 24)) / APROGD ( APROG data (No. 25))
Parameter Step 1
Parameter Step 2
Fig. 45
Rec
=
1
Wp0
=
Wert
Tp1
=
Zeit
Wp1
=
Wert
Tp2
=
Zeit
Wp2
=
Wert
Tp3
=
Zeit
Wp3
=
Wert
Tp4
=
Zeit
.
.
.
Wpn
=
Wert
Tpn+1 =
--:--
Ende
scrollin
g
Fig. 46