CALLPG (Function for calling up an operating page (no. 127))
With function block CALLPG, which can be used only once, event-triggered call-up of a particular operating page is
possible, unless an operation is being carried out on this page (waiting time 5 s). The required operating page is deter -
mined by the number of its function block. The block number is applied to input Bl-no of CALLPG.
Switch-over is with the positive edge of the logic signal at digital input d1 of CALLPG. It permits e.g. changing to a par -
ticular operating page in case of an exceeded limit value.
Exceptions: Switching over is omitted with:
active operation by the operator. Page changing is delayed and occurs only 5 seconds after the last key pressure.
a wrong page number, or if the page is blocked at activation time.
Unless the page which should be activated is available the page survey is displayed.
When leaving the operating page called up via CALLPG, the previously active operating page is displayed again.
Following functions blocks have an operating page APROG, DPROG, CONTR, CONTR+, PIDMA, VWERT, VBAR, VTREND,
VPARA, ALARM
+
With activation by CALLPG from an already selected page, this page is not called up again. I. e. if a sub-page was se -
lected, the multifunction unit remains on this page.
+
With multiple page changing by activation of CALLPG, the sequence is not buffered. After leaving the page(s) activated
by CALLPG the initial menu page is displayed again.
+
In case of CALLPG whilst the multifunction unit is not at operating level (main menu: Parameter, .., Miscellaneous),
CALLPG call remains active in the background. Changing to the operating page activated by CALLPG is done when se -
lecting the operating level for the next time.
Digital input
d1
Positive edge causes change to the operating page set at Bl-no
Analog input
Bl-no
Number of the operating page which should be displayed