beautypg.com

Dpwrit 172, Level1 data writing via profibus 172, Write level1 data via profibus 172 – West Control Solutions KS98-1 User Manual

Page 172: General, Inputs/outputs

background image

III-10.4

DPWRIT ( write level1 data via PROFIBUS (No. 103))

General

Block numbers 11...14. The data of a PROFIBUS data channel are transmitted into the memory. Block number 11 trans -
mits the data of channel 1, block number 12 transmits the data of channel 2, etc. The PROFIBUS module writes the
data of two channels at intervals of 100ms. The data set comprises 6 analog process values (y1...y6) and 16 digital sta -
tus informations (z1...z16), which are available to the engineering. The digital outputs (b-err, p-err, c-err, d-err and
valid) indicate the PROFIBUS status.

g

Further information on communication with PROFIBUS is given in the interface description (order no.: 9499 940 52711).

Inputs/outputs

Digital outputs:
z1 ... z16

Digital process values, which can be written via the Profibus.

b-err

PROFIBUS status: 1 = bus access not successful

p-err

PROFIBUS status: 1 = faulty parameter setting

c-err

PROFIBUS status: 1 = faulty configuration

d-err

PROFIBUS status: 1 = no data communication

valid

PROFIBUS status: 1 = data o.k.

Analog outputs:
y1 ... y6

Analog process values, which can be written via the Profibus.

Communication

9499-040-82711

III-172

DPWRIT ( write level1 data via PROFIBUS (No. 103))

z1

z16

...

y1

.

.

.

.

.

y6

Interface

(0)

(1)

(2)
(3)
(4)
(5)
(6)
(7)

7 6 5 4 3 2 1 0

7 6 5 4 3 2 1 0

b-err
p-err
c-err
d-err
valid