Iii-8 limit value signalling and limiting 146, Alarm and limiting with fixed limits 146, Allp 146 – West Control Solutions KS98-1 User Manual
Page 146: Limiting and limit value signalling 146, Iii-8 limit value signalling and limiting
III-8
Limit value signalling and limiting
III-8.1
ALLP ( alarm and limiting with fixed limits(No. 40))
Signal limiting:
Parameter L1 determines the minimum, H1 the maximum limiting. y1 is limited to the range between L1 and H1. (L1 ß
y1 ß H1). With parameter H1 smaller than L1, a higher priority is allocated with H1. This means that y1 is ß H1.
Limit signaller:
The limit signaller has two 2 low and high alarms (L1, L2, H1 and H2). Configuration parameter
Select can be
used to select the variable to be monitored (
x1, dx1/dt, x1 - x0).
The limit values are freely adjustable as parameters and have an adjustable hysteresis of ? 0.
The smallest separation between a minimum and a maximum limit value is 0.
When an alarm is triggered, the corresponding output (L1, L2, H1 and H2) is logic “1".
D -alarm (
dx1/dt)
Value x1(t-1) measured one sampling interval before is subtracted from instantaneous value x1(t). This difference is di -
vided by calculation cycle time Tr (100, 200, 400, 800ms).
Thus input variable x1 can be monitored for its rate of change.
9499-040-82711
Limit value signalling and limiting
ALLP ( alarm and limiting with fixed limits(No. 40))
III-146
Select
H1
H2
L2
L1
x1
Y1
h1
h2
l1
l2
Xsd
x0
_
H2
L1
H1
Fig. 9 Limiting at H1 < L1