beautypg.com

West Control Solutions KS98-1 User Manual

Page 294

background image

Output

Description

Minute

Minute of the real-time clock 0...59

Hour

Hour of the real-time clock 0...23

Day

Day of the real-time clock 0...31

Month

Month of the real-time clock 1...12

Year

Year of the real-time clock 1970....2069

Week-D

Weekday of the real-time clock 0...6 = Su...Sa

Langu

Language German = 0 language English = 1 Language selection is in

Miscellaneous, Device data

PageNo

Output of the number of the function block the operating page of which is displayed instantaneously. ”0” means
that no operating page is displayed.

SysErr

Start-up problem. Unlessthis output is ”0”, a start-up error occurred (corresponds to KS 98-1 start-up error dis-
play). Bit assignment: Bit 1 = reset command, bit 2 = quartz, bit 4 = halt, bit 5 = SW watchdog (endless loop); the
other bits are not used.

Digital outputs

c-hide

= 1 configuration change disabled

p-hide

= 1 parameters/configurations disabled

m-hide

= 1 The main menu is not displayed, the operating pages are displayed only during online mode

b-block = 1 the use of the bus interface is blocked
switch

S.I.L. switch open = 0 closed = 1. This information permits blocking via the hardware.

fail

= 1 common message sensor error of inputs AINP1...AINP6

safe

= 1 safety status set via interface with code 22, Fbno. 0, Fctno. 0

Pwrchk

Power-fail check. This value is always reset (0) by KS 98-1 after power-on. It can be set to active (1) by a signal at
the digital input to permit detection of a temporary power failure.

start

With change from offline to online, start is 1 during 800 ms. During this time, all time groups were calculated at
least once.

dperr

Collected error messages Profibus

clock

1 = real-time clock provided, 0 = no real-time clock option.

fkey

Status of the function key

Ò

¹) These outputs are = 0 if real-time clock option B with RS 422 is missing.

Powerup KS98/98-1

Start-up behaviour after power recovery.

The procedure is as follows:

Ü

All blocks are initialized. Unless a special start-up behaviour is configured (see programmer), the two possibili -
ties are:
a. The memory contents are still unchanged. The block outputs keep the value before power failure.
b. After prolonged power failure, the memory contents are destroyed. The function blocks are initiated

regardless of the function inputs.

*

All input functions are calculated once.

Ö

The start bit of the status block is set to 1.

ä

All blocks are calculated at intervals of 1.6 seconds (16 cycles of the 100ms time slot) in the order of block

numbers.

#

The start bit of the status block is set to 0.

9499-040-82711

Additional functions

STATUS ( status function (No. 125))

III-294