Analog input module 178 - 179, Rm_ai 178 - 179 – West Control Solutions KS98-1 User Manual

Page 178

background image

Digital outputs

et-err

0 = no engineering error detected

1 = engineering error (several RM module functions at a slot)

slotId

0 = correct slot assignment

1 = faulty slot assignment (faulty RM module fitted)

valid

0 = no data

1 = data could be received

di 1

...

di 8

1st to 8th digital input signal

Parameter and configuration data

Configuration

Description

Range

Default

MTyp

Module type

0: RM251 = 8 x 24 VDC, 0,5 A

0

1: RM252 = 4 x relay (230 VDC) 2 A

Inv1

Direct or inverse output of input signal 1?

direct

direct

...

...

/

Inv8

Direct or inverse output of input signal 8?

inverse

FMode1

Output last signal or

FState in case of

communication failure?

no r no particular reaction

no

...

/

FMode8

FStat value output

FState1

Output status in case of error

0/1

0

...

FState8

a

Note related to hardware type RM 251
The outputs are monitored pairwisely. To avoid faulty displays, unused outputs should be short circuited.

III-11.5

RM_AI (RM200 - analog input module (No. 17))

Function

RM_AI handles the data from connected analog input modules.

Inputs and outputs

Analog input

Slotx

Connection of one of the

slot outputs of the RM200 node (C_RM2x)

Digital outputs

et-err

0 = no engineering error detected

1 = engineering error (several RM module functions at a slot)

slotId

0 = correct slot assignment

1 = faulty slot assignment (faulty RM module fitted)

valid

0 = no data

1 = data could be received

fail 1

...

fail 8

Measurement error at channel 1 to 4 (e.g. sensor break)

tcfile

Temperature compensation error

Analog outputs

Ai 1...Ai 4 1st to 4th analog input signal

I/O extensions with CANopen

9499-040-82711

III-178

RM_AI (RM200 - analog input module (No. 17))