Digital output module 177, Rm_di 177, Rm_do 177 – West Control Solutions KS98-1 User Manual
Page 177: Rm200 digital input module 177
III-11.3
RM_DI (RM 200 - (digital input module (No. 15))
Function
RM_DI handles the data from the connected digital input modules.
Inputs and outputs
Analog input
Slotx
Connection of one of the slot outputs of the RM200 node (C_RM2x)
Digital outputs
et-err
0 = no engineering error
detected
1 = engineering error (several RM module functions at a slot)
slotid
0 = correct slot assignment
1 = faulty slot assignment (wrong RM module inserted)
valid
0 = no data
1 = data could be received
di 1
...
di 8
1st to 8th digital input signal
* Slot = conn.-no., socket e.g. 2...10
Parameter and configuration data
Configuration
Description
Value
Default
MTyp
Module type
0: RM241 = 4 x 24 VDC
0
1: RM242 = 8 x 24 VDC
2: RM243 = 4 x 243 VAC
Inv1
Direct or inverse output of input signal 1?
direct
direct
...
...
/
Inv8
Direct or inverse output of input signal 8?
inverse
III-11.4
RM_DO (RM 200 - digital output module (No. 16))
Function
RM_DO handles the data from connected digital output modules.
Input and output modules
Analog input
Slotx
Connection of one of the slot outputs of the RM200 node (C_RM2x)
Digital inputs
do 1...do 8 s for digital inputs 1 to 8
9499-040-82711
I/O extensions with CANopen
RM_DI (RM 200 - (digital input module (No. 15))
III-177