West Control Solutions KS98-1 User Manual
Page 196
Digital inputs:
r/w
access mode : 0 = read, 1 = write
Analog inputs:
Node
decimal CAN-nodeaddress,1..42
(KS 98-1 is the CAN Object Identifier according to CiA DS301, node ID + 600H)
D-Type
datatype of the connected value, 0..6. Following datatypes are available:
0:
Uint8
1:
Int8
2:
Uint16
3:
Int16
4:
Uint32
5:
Int32
6:
Float
SubInd
address in object directory 1..255
Index
address in object directory 1..65535
X1writ
data value (–29999 ... 999999)
Digital outputs:
err
0 = no error
1 = error detected.
ready
0 = transmission is being handled. So far, no confirmation was received.
1 = transmission completed. Ready for the next command.
Analog outputs:
T1 1...T1 8
1st to 8th analog output value in byte format (8-bit) for COB-ID 1
T2 1...T2 8
1st to 8th analog output value in byte format (8-bit) for COB-ID 2
Parameters (can be changed during operation):
Access
access mode: 0 = read, 1 = write
NodeId
decimal CAN node address,1..42
(KS98-1 forms the CAN Object Identifier according to CiA DS301, node ID + 600H)
D-Type
data type of the connected value, 0..6. The following data types are available
0:
Uint8
1:
Int8
2:
Uint16
3:
Int16
4:
Uint32
5:
Int32
6:
Float
SubInd
address in object directory 1..255
Index
address in object directory 1..65535
Wert
data value –29999 ... 999999)
Possible errors (on output err):
w
Faulty KS 98-1 hardware. KS98-1 CAN expected.
w
The trigger input is not connected.
w
No reply or faulty reply from the instrument.
w
Instrument replies an inquiry with an error message.
w
Min. one parameter or connected value is out of limits.
Description of KS 98-1 CAN bus extension
9499-040-82711
III-196
CSDO (CAN-SDO function (No. 92))