Digital inputs:

r/w

access mode : 0 = read, 1 = write

Analog inputs:

Node

decimal CAN-nodeaddress,1..42
(KS 98-1 is the CAN Object Identifier according to CiA DS301, node ID + 600H)

D-Type

datatype of the connected value, 0..6. Following datatypes are available:

0:

Uint8

1:

Int8

2:

Uint16

3:

Int16

4:

Uint32

5:

Int32

6:

Float

SubInd

address in object directory 1..255

Index

address in object directory 1..65535

X1writ

data value (–29999 ... 999999)

Digital outputs:

err

0 = no error
1 = error detected.

ready

0 = transmission is being handled. So far, no confirmation was received.
1 = transmission completed. Ready for the next command.

Analog outputs:

T1 1...T1 8

1st to 8th analog output value in byte format (8-bit) for COB-ID 1

T2 1...T2 8

1st to 8th analog output value in byte format (8-bit) for COB-ID 2

Parameters (can be changed during operation):

Access

access mode: 0 = read, 1 = write

NodeId

decimal CAN node address,1..42
(KS98-1 forms the CAN Object Identifier according to CiA DS301, node ID + 600H)

D-Type

data type of the connected value, 0..6. The following data types are available

0:

Uint8

1:

Int8

2:

Uint16

3:

Int16

4:

Uint32

5:

Int32

6:

Float

SubInd

address in object directory 1..255

Index

address in object directory 1..65535

Wert

data value –29999 ... 999999)

Possible errors (on output err):

w

Faulty KS 98-1 hardware. KS98-1 CAN expected.

w

The trigger input is not connected.

w

No reply or faulty reply from the instrument.

w

Instrument replies an inquiry with an error message.

w

Min. one parameter or connected value is out of limits.

Description of KS 98-1 CAN bus extension

9499-040-82711

III-196

CSDO (CAN-SDO function (No. 92))