beautypg.com

Rate-of-change limiting 151, Velo 151, Iii-8.4 velo ( rate-of-change limiting (no. 43) ) – West Control Solutions KS98-1 User Manual

Page 151: Inputs/outputs, Parameters

background image

III-8.4

VELO ( rate-of-change limiting (No. 43) )

The function passes input variable x1 to output y1 and limits its rate of change dx1/dt to a positive and negative gradient.

The gradients can be adjusted either as parameter

GrX+ and Grx- or preset at analog inputs GrX+ and Grx-.

Switch-over between the gradient sources is by parameter

Mode+ for the positive gradient and by Mode- for the

negative gradient.

Via digital inputs d1 and d2, limiting can be switched off separately for positive and negative rates of change.
When using the analog inputs for gradient adjustment, the following is applicable:
GrX+ ? 0 or GrX- ß 0 otherwise the relevant gradient is set to 0.

+

The function has a ‘memory’. This means: after power-on, it continues operating with the value of y1 which existed at
power-off, provided that the RAM data are still unchanged.

Inputs/outputs

Digital inputs
d1

Control of positive gradient 0 = the selected gradient is effective. 1= gradient =

Î

d2

Control of negative gradient 0 = the selected gradient is effective. 1= gradient = -

Î

Analog inputs

x1

Input variable to be limited

GrX+

positive gradient [

1

/s

] with parameter Mode+ = Inp. GrX+

GrX-

negative gradient [

1

/

s

] with parameter Mode- = Inp. GrX-

Analog output
y1

Limited input value x1

No configuration parameters!

Parameters:

Parameter Description

Range

Default

Mode+

Source of positive gradient

parameter

GrX+

Para.GrX+

t

analog input

GrX+

Inp. GrX+

Mode-

Source of negative gradient

parameter

GrX-

Para.GrX-

t

analog input

GrX-

Inp. GrX-

Grx+

positive gradient [

1

/

s

] with parameter

Mode+ = Para.GrX+

0 ... 999 999

0

Grx-

negative gradient [

1

/

s

] with parameter

Mode- = Para.GrX-

-29 999 ... 0

0

Limit value signalling and limiting

9499-040-82711

III-151

VELO ( rate-of-change limiting (No. 43) )

d2
d1
x1

y1

Mode+

GrX+

GrX+

Mode-

GrX-

GrX-

О

О