Iii-9.3 vbar ( bargraph display (no. 97) ) 161, Bargraph display 161, Vbar 161 – West Control Solutions KS98-1 User Manual
Page 161: Iii-9.3 vbar ( bargraph display (no. 97) )
III-9.3
VBAR ( bargraph display (No. 97) )
General
This function permits the display of 2 analog input signals as bargraphs, and of 2 analog input signals as numeric valu -
es. Moreover, two analog output signals can be defined. Another 4 analog inputs can be used to position 2 markings
at each side of the bar within the bargraph range. These markings can be e.g. alarm limits or reference values. With
open marker inputs, or out-of-range marker values, display of markers is suppressed.
w
Determination of horizontal or vertical bargraph is via configuration (type).
w
Determination if value displays are visible or switched off
w
Configuration of start values x3mid or x4mid determines, if the bargraph points only in one direction (from top or
bottom) or in 2 directions from the middle.
w
The values applied to the inputs are displayed.
w
A value which is adjustable via the front panel is output at the relevant analog output.
w
Changing these values from the operating level can be suppressed.
w
Parameters
Y1/Y2 are the initial values for Power-On.
w
The output value is displayed only with the output fed back to the relevant input, or if the display for this value is
in the adjustment mode.
w
Value changes are stored as parameters
Y1 / Y2 in non-volatile EEPROM.
Visualization
9499-040-82711
III-161
VBAR ( bargraph display (No. 97) )