III-13.1

C_KS8x (KS 800 and KS 816 node function - (No. 58))

Node function

C_KS8x provides the interface to one of the multi-channel temperature controllers KS 800 or KS 816.

Analog outputs

C1 … C16 can be used to connect the KS8x functions, which represent each a controller of KS

800 (max. 8 controllers) or of KS 816 (max. 16 controllers).

Unlike the other KS 98-1 functions, only one data function can be soft-wired to each analog o utput.
Prerequisite for communication of KS98-1 multi-function unit and KS800 or KS816 is the complying adjustment of the
CAN parameters. (r see *1)).

Outputs

Analog inputs

C1...C16 Connection of the KS8x functions (single controllers in KS800 / KS816)

Digital outputs

et-err 0 = no engineering error

1 = engineering error (different node function at the same KS800)

id-err 0 = correct node

1 = faulty node Id (no KS800 / KS816 replied under the configured
node ID)

valid

0 = no data

1 = data were received

online 0 = KS800/816 is off-line

1 = KS800/816 is on-line

fail 1 0 = no fail at do1...do12

1 = fail at do1...do12

fail 2 0 = no fail at do13...do16

1 = fail at do13...do16

fail 3 0 = no heating current short circuit

1 = heating current short circuit

di1

di1status

di2

di2 status

di3

di3 status

di4

di4 status

Parameter und Konfigurationsdaten

Configuration

Description

Range

Default

NodeId

KS800/KS816 node address

2...42

2

a

The data from the various controllers are read cyclically.
Maximally at intervals of 1.6 seconds (KS800) or 3.2 seconds (KS816), all data are updated.

* 1) The parameters for the CANopen bus are adjustable in engineering tool window "CANparameter” or via the

instrument parameters on the front panel (ET98 r Device r CANparameter).

Connection of KS 800 and KS 816

9499-040-82711

III-186

C_KS8x (KS 800 and KS 816 node function - (No. 58))