Three-point controller 232, Three-point controller – West Control Solutions KS98-1 User Manual
Page 232
Three-point controller
Switching controller with three switching statuses:
1. Heating switched on;
r output Y1 = 1, Y2 = 0
2. Heating and cooling switched off;
r outputs Y1 = 0, Y2 = 0
3. Cooling switched on;
r outputs Y1 = 0, Y2 = 1
E.g. for temperature control with electrical heating (h) and cooling (c).
Adjust cycle time
Tp1 and Tp2 as follows:
Tp
Tu
1
0 25
<=
·
,
(h) Tp
Tu
2
0 25
<=
·
,
(c).
With higher
Tp1/Tp2, oscillations have to be expected. Cycle times Tp1 and Tp2 are the minimum cycle times
at 50% duty cycle.
PD/PD action
(
Tn = 0 = switched off Tn = Î)
The positioning range reaches from 100 % heating (Y1) to 100 % cooling (Y2). The proportional bands must be adapted to the
various heating and cooling power values. In order to keep the control variable constant, a defined amount of energy depen-
dent of is required. This causes a permanent control deviation, which increases with growing X
p(1,2).
DPID/DPID action
By means of the I action, line-out without permanent control deviation is possible. Transition from trigger point 1 (hea-
ting) to trigger point 2 (cooling) is without neutral zone. The proportional bands must be adapted to the various heating
and cooling power values.
Fig.: shows the static characteristic for inverse output action.
Direct/inverse switchover only causes exchanging of the outputs for “heating/cooling”.
Expressions “heating” and “cooling” may also mean similar processes (dosing acid/lye, ...).
The neutral zone is adjustable separately for the trigger points (X
sh1
, X
sh2
) i.e. it need not be symmetrical to the .
The type of positioning signals is selectable:
CFunc = 3-point
heating switching,
cooling switching
CFunc = cont/switch
heating continuous,
cooling switching
CFunc = switch/cont
heating switching,
cooling continuous
Combination “heating continuous” and “cooling continuous” is covered by “splitRange - continuous controller with
split-range behaviour”. r see also "continuous controller" page: 238.
Controller
9499-040-82711
III-232
Control behaviour
Output Y1 (heating)
Output Y2 (cooling)
Process value
Setpoint
Setpoint
100%
0%
100%
0%
Y1Â h
Y2Â c
Xn100
Xn0
W0
Weff
W100
Xeff
Xp2
Xp1=Xp'+Xp''
Xp'
Xp''
Xsh1 Xsh2
actual
working point
Fig.: 56
Static operating principle
of a three-point controller