Time functions
III-6.1
LEAD ( differentiator (No. 50))
The differentiator forms the difference quotient according to equation:
( )
(
)
( )
(
)
{
}
[
]
y t
T
T
T
y t
t
a
x t
x t
t
y
s
s
s
1
1
1
1
0
=
+
Ч
-
+ Ч
-
-
+
ts
sampling interval
x1(t)
instantaneous x1
T
time constant
x1(t-ts)
previous x1
a
gain
y1(t)
instantaneous y1
y0 output offset
y1(t-ts)
previous y1
C
T
T
Ts
=
+
<1
( differentiation constant )
The complex transfer function reads:
F
a T p
T p
p
( )
= Ч Ч
Ч +1
Inputs/outputs:
Digital input
reset
= 1 causes that y1= y0 and the difference quotient is set to 0.
= 0 starts differentiation automatically.
Analog input
x1
Input variable to be differentiated
Output
y1
Differentiator output
Parameters:
Parameters
Description
Range
Default
a
Gain factor
-29 999...999 999
1
y0
Output offset
-29 999...999 999
0
T
Time constant in s
0...199999
1
Configuration:
Configuration
Description
Value
Default
Mode
Differentiator
operation
Differentiating all changes
0
0
Differentiating only positive changes
dx/dt >0,
1
Differentiating only negative changes
dx/dt <0
2
9499-040-82711
Time functions
LEAD ( differentiator (No. 50))
III-124
a
T
x1
reset
y1
y0