beautypg.com

Controlling a program 39, Parameter setting 39, Scrolling – West Control Solutions KS98-1 User Manual

Page 39

background image

Controlling a program

Press key H to control the program sequence:

The time curve can be controlled also by changing the
elapsed time c or segment number £ (preset).

+

Dependent on engineering, parts of this operation may
be changed or disabled.

Program parameter setting

Select the program for editing via field "Rec" ¡. Call up the
relevant s/control values, segment times and types with
menu item “program” in the status line (field — ).

A page on which the selected program is displayed as
“RecEdt” is opened. The parameters are listed in the order
of segments.

The data blocks are displayed dependent on engineering.
The type of individual segments can be changed dependent
on data block type.

Selection of all programs including the inactive ones is
possible on line

RecEdt in any programmer status.

When using recipe names, these names are displayed on
the editing page. Switching over to the parameters of a dif-
ferent recipe can be done by altering the recipe name. This
is possible at any time and does not cause switchover of
the active recipe.

A segment list is completed with end identification
--:-- in parameter Tp

n

of the last segment. When set-

ting the last segment time T

n

to a valid value (higher or

equal to 0), the next parameter is displayed automatically
T

n+1

. =

--:-- etc.

This procedure permits shortening of a current program by
adjusting a value < 0 in the required position for T

n

=

--:-- with key D.

The following segments will be suppressed in the program.
The relevant segment parameters remain unchanged and
can be re-activated by input of a valid value for T

n.

9499-040-82711

Operating pages

Programmer

I-39

RUN

RUN

RESET

STOP

END

RESET

H

H

H

Rec

=

1

Wp0

=

Wert

Tp1

=

Zeit

Wp1

=

Wert

Tp2

=

Zeit

Wp2

=

Wert

Tp3

=

Zeit

Wp3

=

Wert

Tp4

=

Zeit

.

.

.

Wpn

=

Wert

Tpn+1 =

--:--

Ende

scrolling

Fig. 21

Parameter Step 1

Parameter Step 2