Remaining segment time
The remaining time of the actual segment is displayed on the operating page.
It is:
• readable via interface
• available as an additional analog output signal
• always 0 with reset
• suppressed with "preset to segment"
Incompatibility to earlier KS 98 functionality
Recipe switchover:
KS 98: The receipe number can be switched over at any time on the programmer operating page. However, the new se -
lected recipe will be effective only after the next reset. On the subordinated parameter page, switching over has the
same effect.
KS 98-1: On the programmer operating page, the recipe number can be switched over only during reset status. Swit -
chover is effective immediately. On the subordinated operating page, switching over continues being possible at any
time. Nevertheless, only the recipe to be displayed with its parameters is switched over. The instantaneously active re -
cipe remains unaffected.
End behaviour with PEnd = ’stop‘:
KS 98: Program is at the end, status is ’run‘, reset command leads to an immediate re-start
KS 98-1: Program stands at the end, status is ’stop‘, the program remains in reset status after a reset command.
Segment number at program end:
KS 98: At program end, the number of the last segment is displayed as segment number (SegNo output, operating
page, interface).
KS 98-1: At program end, the number of the last segment + 1 is displayed as segment number (SegNo output, opera -
ting page, interface), in order to bring also any slave programmer to the end status.
Programmer
9499-040-82711
III-218
APROG ( analog programmer (No. 24)) / APROGD ( APROG data (No. 25))