I-11.5 i/o-test 50, I-11.5 i/o-test – West Control Solutions KS98-1 User Manual
Page 50
I-11.5
I/O-Test
Input and output type and measuring/signal range are configurable.
For this, switch the unit to OFFLINE(r page 35) first after starting up. All inputs and outputs are preset to 0 .. 20mA
and 0-100% value range.
Before commissioning, the inputs and outputs to be connected must be configured for the required sensor type via
main menu “Configuration”.
+
After adjusting the correct type, the unit must be switched back to ONLINE!
Now, KS98-1 is ready for the first input/output test.
Possible settings:
w
AINP1: thermocouple types; Pt100; 2*Pt100; 0/4 .. 20mA; 0/2 .. 10V; transducer 500
W; resistance 500W 250W
w
AINP3 (option C): 0/4 .. 20mA
w
AINP4 (option C): 0/4 .. 20mA
w
AINP5
: 0/4 .. 20mA
w
AINP6
: 0/4 .. 20mA
w
OUT1
: 0/4 .. 20mA or relay
w
OUT2
: 0/4 .. 20mA or relay
w
OUT3 (option C) : 0/4 .. 20mA
w
OUT4
: relay
w
OUT5
: relay
Dependent on instrument selection, outputs OUT1 and OUT2 can be relay or current output. Accordingly, they must be
controlled digitally or analoguely in the engineering.
As all outputs were defined as analog outputs in the present engineering, a value below 50% (corresponds to logic
“0”) and a value above 50% (corresponds to logic “1”) must be set for relay output testing.
Outputs OUT4 and OUT5 are always relays, i.e. they are controlled digitally on the relevant operating page. (Adjusting
values r Navigation page 32).
Adjusting the output values and selecting the pages are done as described. Continuation pages are selected using
keys ID via the menu lines (
p, q) and called up with M.
This engineering is not suitable for controlling a plant. For this purpose, a customer-specific engineering is required
(see versions, section: Adjustment on page 18).
a
Faulty settings can cause damage to instrument and plant!
Maintenance, test, trouble shooting
9499-040-82711
I-50
I/O-Test