Connections, Inputs – West Control Solutions KS98-1 User Manual
Page 13
Connections
Depending on version and selected options, the following inputs
and outputs are available:
DI
DO
AI
AO
4 relays
or
2 relays
+
2 AO
di1*
di2*
OUT1
OUT2
OUT4
OUT5
INP1
INP5
INP6
–
di1*
di2*
OUT4
OUT5
INP1
INP5
INP6
OUT1
OUT2
OPTION B
di3
di4
di5
di6
di7
do1
do2
do3
do4
–
–
OPTION C*
or
di8
di9
di10
di11
di12
do5
do6
INP3
INP4
OUT3
modular
OPTION C*
Depending on module type
* Not available with option CAN!
Inputs
Universal input INP1
Limiting frequency: fg = 1 Hz, Measurement cycle: 200 ms
Thermocouples
according to DIN IEC 584
Type Range
Error
Resolution
L
–200...900°C
£ 2K
0,05 K
J
–200...900°C
£ 2 K
0,05 K
K
–200...1350°C
£ 2 K
0,072 K
N
–200...1300°C
£ 2 K
0,08 K
S
–50...1760°C
£ 3 K
0,275 K
R
–50...1760°C
£ 3 K
0,244 K
B
1)
(25)400...1820°C
£ 3 K
0,132 K
T
–200.. .400°C
£ 2 K
0,056 K
W(C)
2)
0...2300°C
£ 2 K
0,18 K
E
–200... 900°C
£ 2 K
0,038 K
* 1 ) from 400 °C
* 2 ) W5Re/W26Re
With linearization (temperature-linear in °C or °F)
Input resistance:
³ 1MW
Cold-junction compensation (CJC): built in
Input circuit monitor:
Current through sensor:
£ 1 mA
Reverse-polarity monitor is triggered at 10 °C below span start.
Additional error of internal CJC
£ 0.5 K per 10 K terminal temperature External temperature
selectable: 0...60 °C or 32...140 °F
Resistance thermometer
Pt 100 to DIN IEC 751, and temperature difference 2 x Pt 100
Range
Error
Resolution
–200.0...250.0 °C
£ 0.5 K
0.024 K
–200.0...850.0 °C
£ 1.0 K
0.05 K
2 x –200.0...250.0 °C
£ 0.5 K
0.024 K
2 x –200.0...250.0 °C
£ 0.1 K
0.05 K
Linearization in °C or ° F
Two wire connection with compensation or three-wire connection
without.
Two-wire connection with lead resistance adjustment.
Lead resistance:
£ 30 W per lead
Sensor current:
£ 1 mA
Input circuit monitoring for sensor/lead break, and lead short circuit.
Potentiometric transducer
R
total
incl. 2 x R
L
Error
Resolution
0...500
W
£ 0.1 %
£ 0.02 W
Resistance-linear
Sensor current:
£ 1 mA
Matching/scaling with sensor connected.
Input circuit monitoring for sensor/lead break, and lead short circuit.
Resistance input
Range
Error
Resolution
0...250
W
£ 0.25 W
< 0.01
W
0...500
W
£ 0.5 W
< 0.02
W
Direct current 0/4...20mA
Range
Error
Resolution
0/4...20 mA
£ 0.1 %
£ 0.8 mA
Input resistance: 50
W
Input circuit monitor with 4...20mA: triggered when I
£ 2 mA
Direct voltage
Range
Error
Resolution
0/2...10 V
£ 0.1 %
£ 0.4 mV
Input resistance
³ 100 kW
9499-040-82711
Technical data
I-13