III-13.2
KS8x (KS 800/ KS 816 controller function - (No. 59))
Each KS8x function handles a controller of KS 800 or KS 816. The analog and digital inputs can be used to send the
control signals to the controller in KS800/16. The analog outputs provide the process and controller values.
Inputs and outputs
Analog inputs
C x
Connection to one of the
C1...C16 outputs of node function C_KS8x
W
Controller
Yman
Correcting variable in manual mode
Digital inputs
a/m
0 = controller is in automatic mode
1 = controller is in manual mode
C off
0 = controller is switched on
1 = controller is switched off
w/w2
0 = controller is in automatic mode
1 = 2nd is active (safety )
we/wi
0 = external is active
1 = internal is active
ostart
0 = don’t start self-tuning
1 = start self-tuning
Digital outputs
et-err
0 = no engineering error
1 = engineering error
(several KS8x controller functions on a controller channel)
valid
0 = no data
1 = data were received
xfail
0 = no sensor fail
1 = sensor fail
Analog outputs
X
Controller process value
Y
Controller correcting variable
St1
Statusbyte 1
For an engineering example to evaluate St1 and St2, see the
next page.
St2
Statusbyte 2
9499-040-82711
Connection of KS 800 and KS 816
KS8x (KS 800/ KS 816 controller function - (No. 59))