Iii-7 selecting and storage 134, Extr 134, Extreme value selection 134 – West Control Solutions KS98-1 User Manual
Page 134: Selection and storage 134, Iii-7 selecting and storage, Iii-7.1 extr ( extreme value selection (no. 30)), Inputs/outputs
III-7
Selecting and storage
III-7.1
EXTR ( extreme value selection (No. 30))
Analog inputs
x1, x2 and x3 are sorted according to their instantaneous values and provided at outputs Max,
Mid and Min. Input value output is at Max for the highest one, at Mid for the medium one and at Min for the
smallest one.
The number of the input with the highest value is output at
MaxNo.
The number of the input with the medium value is provided at output
MidNo.
The number of the input with the smallest value is provided at output
MinNo.
+
With equality, the distribution is at random. Inputs are not included into the extreme value selection, if:
-the input is not wired
-or the input value is higher than 1,5 . 10
37
or smaller than -1,5 . 10
37
.
Number of
failed inputs
Max
Mid
Min
MaxNo
MidNo
MinNo
0
x
max
x
mid
x
min
number of x
max
number of x
mid
number of x
min
1
x
max
x
min
number of x
max
number of x
min
2
the valid value
number of the valid value
3
1,5
. 1037
1,5
. 1037
1,5
. 1037
0
0
0
Inputs/outputs
Analog inputs
x1
...
x3
Input variables to be compared
Analog outputs
Max
Maximum instantaneous input value
Mid
Mean instantaneous input value
Min
Minimum instantaneous input value
MaxNo
Number of maximum instantaneous input value (1 =
x1, 2= x2, 3= x3)
MidNo
Number of mean instantaneous input value
(1 =
x1, 2= x2, 3= x3)
MinNo
Number of minimum instantaneous input value (1 = x1, 2= x2, 3= x3)
9499-040-82711
Selecting and storage
EXTR ( extreme value selection (No. 30))
III-134
Max
MaxNo
Mid
MidNo
Min
MinNo
y1>y2>y3
x1
x2
x3