beautypg.com

Iii-7 selecting and storage 134, Extr 134, Extreme value selection 134 – West Control Solutions KS98-1 User Manual

Page 134: Selection and storage 134, Iii-7 selecting and storage, Iii-7.1 extr ( extreme value selection (no. 30)), Inputs/outputs

background image

III-7

Selecting and storage

III-7.1

EXTR ( extreme value selection (No. 30))

Analog inputs

x1, x2 and x3 are sorted according to their instantaneous values and provided at outputs Max,

Mid and Min. Input value output is at Max for the highest one, at Mid for the medium one and at Min for the
smallest one.

The number of the input with the highest value is output at

MaxNo.

The number of the input with the medium value is provided at output

MidNo.

The number of the input with the smallest value is provided at output

MinNo.

+

With equality, the distribution is at random. Inputs are not included into the extreme value selection, if:

-the input is not wired

-or the input value is higher than 1,5 . 10

37

or smaller than -1,5 . 10

37

.

Number of
failed inputs

Max

Mid

Min

MaxNo

MidNo

MinNo

0

x

max

x

mid

x

min

number of x

max

number of x

mid

number of x

min

1

x

max

x

min

number of x

max

number of x

min

2

the valid value

number of the valid value

3

1,5

. 1037

1,5

. 1037

1,5

. 1037

0

0

0

Inputs/outputs

Analog inputs

x1

...

x3

Input variables to be compared

Analog outputs

Max

Maximum instantaneous input value

Mid

Mean instantaneous input value

Min

Minimum instantaneous input value

MaxNo

Number of maximum instantaneous input value (1 =

x1, 2= x2, 3= x3)

MidNo

Number of mean instantaneous input value

(1 =

x1, 2= x2, 3= x3)

MinNo

Number of minimum instantaneous input value (1 = x1, 2= x2, 3= x3)

9499-040-82711

Selecting and storage

EXTR ( extreme value selection (No. 30))

III-134

Max
MaxNo

Mid
MidNo

Min
MinNo

y1>y2>y3

x1

x2

x3