Behaviour after power failure
Storage in non-volatile EEPROM for structure, configuration, pa-
rameter setting and adjusted setpoints.
Storage in a capacitor-buffered RAM (typ. > 15 minutes) for data
of time functions (programmers, integrators, counters, ...)
Real-time clock(Option B, RS 422)
Buffer capacitor provides back-up for at least 2 days (typical).
Bus interface (
Option B)
TTL and RS422 / 485-interface
Galvanically isolated, choice of TTL or
RS 422/485 operation.
Number of multi function unitsper bus:
With RS 422/485: 99
With TTL signals: 32 interface modules (9404 429 980x1). Address
range ((00...99)See Documentation 9499-040-82911) .
PROFIBUS-DP interface
According to EN 50 170, Vol. 2.
Reading and writing of all process data, parameters, and configu-
ration data.
Transmission speeds and cable lengths
automatic transm. speed detection, 9,6 kbit/s ...12 Mbit/s
Addresses
0...126 (factory setting: 126).Remote addressing is possible.
Other functions
Sync and Freeze
Terminating resistors
Internally selectable with wire-hook switches.
Cable
According to EN 50 170, Vol. 2 (DIN 19 245T3).
Required accessories
Engineering Set PROFIBUS-DP, consisting of:
w
GSD file, Type file
w
PROFIBUS manual (9499-040-82911)
w
Function block(s) for Simatic S5/S7
Electromagnetic compatibility
Complies with EN 50 081-2 and EN 50 082-2.
Electrostatic discharge
Test to IEC 801-2,
8 kV air discharge
4 kV contact discharge
High-frequency interference
Test to ENV 50 140 (IEC 801-3)
80...1,000 MHz, 10 V/m
Effect:
£ 1%
HF interference on leads
Test to ENV 50141 (IEC 801-6)
0.15...80 MHz, 10 V
Effect:
£ 1%
Fast pulse trains (burst)
Test to IEC 801-4
2 kV applied to leads for supply voltage, and signal leads.
Effect:
£ 5%resp. restart
High-energy single pulses (surge)
Test to IEC 801-5
1 kV symmetric or 2 kV asymmetric on leads for supply voltage.
0.5 kV symmetric or 1 kV asymmetric on signal leads.
9499-040-82711
Technical data