8041 enclosure voltage over, 8042 enclosure voltage under, 8043 enclosure voltage unknown – Avago Technologies 3ware SAS 9750-16i4e User Manual
Page 301

Error and Notification Messages
www.lsi.com/channel/products
289
8041 Enclosure voltage over
Event Type
Error.
Cause
Applies to 9750 and 9690SA controllers.
The enclosure power supply voltage is higher than the normal range.
Action
This error is rare. If you see it you may need a UPS or voltage regulator to
stay within the recommended voltage range.
8042 Enclosure voltage under
Event Type
Error.
Cause
Applies to 9750 and 9690SA controllers.
The enclosure power supply voltage is lower than the normal range. This can
be due to a failing power supply or an unreliable power source.
Action
If due to a failing power supply, replace it as soon as possible.
It is recommended to use an uninterruptible power supply (UPS) to protect
against power failures.
8043 Enclosure voltage unknown
Event Type
Warning.
Cause
Applies to 9750 and 9690SA controllers.
The enclosure is not reporting voltage data. This can be due to a failing power
supply.
- 3ware SAS 9750-24i4e 3ware SAS 9750-4i 3ware SAS 9750-4i4e 3ware SAS 9750-8e 3ware SAS 9750-8i 3ware 8006-2LP 3ware 8006-2LP (Channel) 3ware 9550SXU-4LP 3ware 9550SXU-4LP (Channel) 3ware 9550SXU-8LP 3ware 9550SXU-8LP (Channel) 3ware 9650SE-12ML 3ware 9650SE-12ML (Channel) 3ware 9650SE-16ML 3ware 9650SE-16ML (Channel) 3ware 9650SE-24M8 3ware 9650SE-24M8 (Channel) 3ware 9650SE-2LP 3ware 9650SE-2LP (Channel) 3ware 9650SE-4LPML 3ware 9650SE-4LPML (Channel) 3ware 9650SE-8LPML 3ware 9650SE-8LPML (Channel) 3ware 9690SA-4I 3ware 9690SA-4I (Channel) 3ware 9690SA-4I4E 3ware 9690SA-4I4E (Channel) 3ware 9690SA-8E 3ware 9690SA-8E (Channel) 3ware 9690SA-8I 3ware 9690SA-8I (Channel)