0019 drive removed, 001a drive inserted – Avago Technologies 3ware SAS 9750-16i4e User Manual

Page 259

background image

Error and Notification Messages

www.lsi.com/channel/products

247

The 3ware RAID controller supports SMART monitoring for SATA and SAS
drives, whereby the individual drives automatically monitor certain
parametric information such as error rates and retry counts. This type of
monitoring may be able to predict a drive failure before it happens, allowing
you to schedule service of the unit before it becomes degraded. The SMART
status of each drive attached to the 3ware RAID controller is monitored daily.

Action

LSI recommends that you replace any drive that has exceeded the SMART
threshold.

If the drive is part of a redundant unit, remove the drive through 3DM2 or
CLI. Replace the drive and start a rebuild.

If the drive is not part of a redundant unit, then you will need to backup your
data before replacing the drive.

See Also

“Viewing SMART Data About a Drive” on page 144

“Rebuilding Units” on page 154

0019 Drive removed

Event Type

Warning

Cause

A drive was physically removed from the controller while the controller was
powered on.

Action

If the drive is not part of a redundant unit, return the drive as soon as possible.
You may need to rescan the controller to have the drive recognized. If at all
possible, do not remove a drive from a non-redundant unit as this may cause
data loss or a system hang.

001A Drive inserted

Event Type

Information