beautypg.com

GW Instek APS-1102A User Manual User Manual

Page 28

background image

APS-1102A User Manual

APS-1102A

2-4

Conditions of installation site

 The APS-1102A should be used indoors, and at altitude up to 2000 m.

 The APS-1102A uses a fan for forced-air cooling. To allow for ample air flow, be sure to

maintain a gap of at least 50 cm between the air inlets and outlets along the sides and rear of

this product and walls or other obstructions.

 Do not stack the product on top of the other, or place it in front or back of the other

(arrangement which makes the cabinet placed behind inhale the exhaust heat of the other).

 Install this product in a location that meets the following conditions for temperature and

humidity ranges.

Operation

guarantee

0°C to +40°C

5% to 85%RH
Absolute humidity of 1 g/m

3

to 25 g/m

3

, no condensation.

Performance

guarantee

+5°C to +35°C

5% to 85%RH
Absolute humidity of 1 g/m

3

to 25 g/m

3

, no condensation.

Storage

condition

10°C to +50°C

5% to 95%RH
Absolute humidity of 1 g/m

3

to 29 g/m

3

, no condensation.

Product reliability may decline in extreme temperature and/or humidity environments. An

environment of approximately 25°C and 50%RH is recommended.

Figure 2-1 illustrates these ambient temperature and humidity ranges.