Recipe Control Register (RECR)

Bit Number

Function

0

Recipe number change

1

Read recipe (PLC → HMI)

2

Write recipe (HMI → PLC)

3

Recipe group number change

4~7 Reserved

8~15

Designate change recipe group number

„

Control Flag for Changing Recipe Number

There are two kinds of methods for changing and calling recipe number. One method is to use HMI

internal register, RCPNO directly. RCPNO is the internal system register used for designating recipe

number. The other method is to use Recipe Control Register (RECR) (Dn+5). When the user wants to

change HMI recipe number, i.e. RCPNO value through control block settings, first, it needs to write

recipe number (N) into Designated Recipe Number Register (RBIR) (Dn+6, please refer to the

explanation of Register for Designating Recipe Number (RBIR) in Chapter 5) and use this control flag

to trigger Bit 0 of Dn+5 to be ON. After setting, RCPNO will be changed to N automatically. This flag

needs be set to OFF and then ON if the user wants to trigger again.

„

Control Flag for Reading Recipe

The user can change the recipe value of PLC by triggering this control flag (Bit 1 is set to ON). Before

reading a recipe from PLC, the user should designate the recipe number (N) first (Please refer to the

section “Control Flag for Changing Recipe Number” in Chapter 5). Then, trigger this control flag to ON

(Bit 1 is set to ON). After setting, the recipe will be read from PLC and stored in designating area of

HMI. This flag needs be set to OFF and then ON if the user wants to trigger again.

„

Control Flag for Writing Recipe

Before writing a recipe to PLC, the user should designate the recipe number (N) first (Please refer to

the section “Control Flag for Changing Recipe Number” in Chapter 5). Then, trigger this control flag to

ON (Bit 2 is set to ON). After setting, the recipe will be written to PLC. This flag needs be set to OFF

and then ON if the user wants to trigger again.

„

Control Flag for Changing Recipe Group Number

There are two kinds of methods for changing and calling recipe group number. One method is to use

HMI internal register, RCPG directly. RCPG is the internal system register used for designating recipe

group number. The other method is to use Recipe Control Register (RECR) (Dn+5). When the user

wants to change HMI recipe group number through control block settings, first, it needs to write recipe